FP2600-T41 User Manual
3-2
Installation and Wiring
• For easier maintenance and operation, and improved ventilation, be sure
the FP unit is mounted at least 100 mm away from any adjacent structures
or objects.
• The FP uses natural ventilation through its outer shell for cooling. When
installing the unit horizontally or sideways (portrait style), use a fan or air
conditioning unit to prevent overheating.
Vertical Installation
Front
Side
Horizontal Installation
•
When installing the FP sideways, place it so that the Power Terminals point up-
wards.
•
Check that heat from surrounding equipment will not cause the FP to overheat.
•
Do not use the FP2600-T41 in an environment that exceeds 50
o
C.
•
Ensure this unit is located as far away as possible from electromagnetic circuits,
non-fuse type breakers, and other equipment that can cause arcing.
•
When installing the FP unit in a panel with an angled face, the face should not
incline either backwards or forwards more than 30
o
.
less than 30
o
Sideways Installation