When attaching a wire to the GP's rear face FG terminal, (on the Power Input Terminal
Block), be sure to create an exclusive ground.
*1
6
Grounding Precaution
7
Input/Output Signal Line Precautions
Connecting the GP's Power Cord
When connecting the power cord, be sure to follow the procedures given below.
1. Confirm that the GP's Power Cord is unplugged from the power supply.
2. Use a screwdriver to remove the Power Input Terminal Block's clear plastic cover.
3. Unscrew the screws from the middle three (3) terminals, align the Ring Terminals and
reattach the screws.
4. Confirm that the wires are connected correctly.
5. Replace the Power Input Terminal Block's clear plastic cover.
The torque required for fastening the screws is 0.5 to 0.6N•m.
8
Maintenance and Inspection
When the surface or the frame of the display gets dirty, soak a soft cloth in water with
a neutral detergent, wring the cloth tightly, and wipe the display.
• Do not use paint thinner, organic solvents, or strong acid compound to
clean the unit.
• Do not use hard or pointed objects to operate the touch-screen panel,
since it can damage the panel surface.
*1 Use a grounding resistance of 100
Ω
, a wire of 2mm
2
or thicker, or your country's
applicable standard.
•
All GP Input and Output signal lines must be separated from all operating circuit
(power) cables.
•
If this is not possible, use a shielded cable and ground the shield.