For easier maintenance, operation, and improved ventilation, be sure to install the PS-G at least
100 mm [3.94 in.] away from adjacent structures and other equipment.
•
Be sure that the ambient operation temperature and the ambient humidity are within their
designated ranges. (Ambient operation temperature: 0 to 50°C, Ambient humidity: 10 to 90%RH,
Wet bulb temperature: 39°C max.) When installing the PS-G on the panel of a cabinet or
enclosure, “Ambient operation temperature” indicates both the panel face and cabinet or
enclosure’s internal temperature.
•
Be sure that heat from surrounding equipment does not cause the PS-G to exceed its standard
operating temperature.
•
When installing the PS-G in a slanted panel, the panel face should not incline more than 30°.
•
When installing the PS-G in a slanted panel, and the panel face inclines more than 30°, the
ambient temperature must not exceed 40°C. You may need to use forced air cooling (fan, A/C) to
ensure the ambient operating temperature is 40°C or below.
•
The PS-G Series unit does not support longitudinal mounting.
Installing
1
Installation Requirements
100
[3.94]
100
[3.94]
100
[3.94]
100
[3.94]
100
[3.94]
100
[3.94]
100
[3.94]
Unit: mm [in.]
Panel
face
Cabinet
interior
30° or less