Chapter 2 Specifications
2-35
General-Purpose Input (DIN 0 to 3, RST)
Input Voltage
DC12V to 24V
Input Method
Sink / Source Input
Input Current
10mA ( DC24V )
Input Resistance
3.6k
Ω
Input Points
5 points ( common with external
reset input )
Operation
Range
ON voltage
DC10V or more
OFF voltage
DC3V or less
Isolation Method
Photocoupler Isolation
Dielectric Strength Voltage
500V or more
• General-Purpose Input (DIN) level must be 1.5 seconds or longer to be
detected.It may detect under 1.5 seconds.
• Be sure the voltage value between terminals is controlled via the input voltage, so
that the PS-A is operated within its recommended range. If the input voltage
exceeds this range, a malfunction or PS-A damage may occur.
• With Sink/Source input, even if the DIN(-), and RST(-) are positive, and DIN(+),
RST(+) are negative, no problems are created. Be sure to operate the unit within
the recommended voltage range.
(Interface Circuit)
+5V
1.8k
Ω
1/10W
1.8k
Ω
1/10W
R
R
PC357
No polarity - for Sink /
Source input
switch or other
switching device
Cable
DC12V
to 24V
RST(+) pin
#
5
DIN0(+) pin
#
6
DIN1(+) pin
#
13
DIN2(+) pin
#
16
DIN3(+) pin
#
18
RST(-) pin
#
11
DIN0(-) pin
#
12
DIN1(-) pin
#
17
DIN2(-) pin
#
23
DIN3(-) pin
#
24