Chapter 3 Installation and Wiring
3-23
Power Cord Specifications
Wiring
When connecting the power cord, use the following items when performing wiring. (Items are made by
Phoenix Contact.
*1
)
*1
For details, please contact your local Phoenix Contact distributor.
Connecting the Power Cord
(1)
Confirm that the power is not supplied to the PS-A unit.
(2)
Push the Opening button with a small and flat screw driver to open the desired pin hole.
(3)
Insert each pin terminal into its each hole. Release the Opening button to clamp the pin in place.
Power Cord Diameter
0.75 to 2.5mm
2
(18 to 12 AWG)
Conductor Type
Simple or Stranded Wire
*1
*1
If the Conductor’s end (individual) wires are not twisted correctly, the end
wires may either short against each other, or against an electrode.
Conductor Length
• Use copper conductors only.
Recommended Driver
SZS 0.6x3.5 (1205053)
Recommended Pin Terminals
AI 0.75-10GY (3201288)
AI 1-10RD (3200182)
AI 1.5-10BK (3200195)
AI 2.5-12BU (3200962)
Recommended Pin Terminal Crimp Tool
CRIMPFOX ZA3 (1201882)
•
Accompanying AC power supply type connector is CA7-ACCNL-01 from Pro-face or
FKC2.5/3-STF-5.08 is manufactured by Phoenix Contact.
10mm[0.39in.]
L
N
FG
Opening Button
Black
White
Green/Yellow
AC power supply cord