Industrial Personal Computer Connections
62
Grounding Procedure
The Industrial Personal Computer ground has 2 connections:
DC Supply voltage
(see page 65)
or AC Supply voltage
(see page 67)
Ground connection pin
1
Ground connection pin (functional earth connection pin)
2
Supply voltage
3
Grounding strip
4
Switching cabinet
When grounding, follow the procedure below:
Step
Action
1
Check that the grounding resistance is 100
or less.
2
When connecting the SG line to another device, ensure that the design of the
system/connection does not produce a ground loop.
NOTE:
The SG and ground connection screw are connected internally in the
Industrial Personal Computer.
3
Use 2.5 mm
2
(AWG 13) wire to make the ground connection. Create the connec-
tion point as close to the Industrial Personal Computer as possible and make the
wire as short as possible.