background image

Packaged Glycol Chiller Systems  | 

III

PROBLEM 

  

POSSIBLE CAUSES 

  

CORRECTIVE STEPS 

compressor will not run 

Main Switch / Circuit Breaker Open 

Reset Switch / Circuit Breaker 

  

Fuse Blown 

Check Electrical Circuits and Motor Windings 

  

Thermal Overloads Tripped 

  

for shorts or grounds.  Investigate for possible over- 

  

Defective Contactor or Coil 

  

loading.  Replace Fuse or reset Circuit Breaker after 

  

System shut down by Safety Device 

  

fault is corrected. 

  

No Cooling is required 

Reset any tripped thermal overloads,  Check unit 

  

Liquid Line solenoid will not open 

  

closely when unit comes online. 

  

Motor Electrical Trouble 

Repair or replace coil 

  

Loose Wiring 

Determine Type and Cause of shut down and  

  

Circulation Pump Not Running 

  

correct before resetting. 

  

  

  

Wait until Unit calls for Cooling.  Check setting of

  

  

  

  

Thermostat.  Check the Temperature of Glycol Solution. 

  

  

  

Check for Voltage at Solenoid Coil,  replace coil. 

  

  

  

Check motor for opens, short circuit,  or burnout. 

  

  

  

Check all wire junctions,  tighten loose connections. 

  

  

  

Check overload relay on circulation Pump 

Compressor noisy or vibrating 

Liquid Refrigerant Flooding to Crankcase 

Check Superheat Setting of Expansion Valve(s).

  

Worn Compressor 

  

Check the Glycol Solution Percentage,  make 

  

  

  

  

certain that evaporator is not freezing up. 

  

  

  

Replace Compressor 

High Discharge Pressure 

Condenser Water Supply is insufficient or 

Adjust Water Regulating Valve,  investigate ways to 

  

  

temperature is too high. 

  

increase water supply. 

  

Fouled Condenser (Water) 

clean 

  

  

Fouled Cooling Tower 

Purge out non-condensables,  reclaim refrigerant 

  

  

Dirty Condenser Fin or Tube Surface (Air) 

  

and recharge with new refrigerant. 

  

Non-Condensables in System 

Remove excess refrigerant charge 

  

System overcharged with Refrigerant 

Open Valve 

  

Discharge Valve Partially closed 

Check Condenser Rating Tables 

  

High Ambient Conditions 

  

  

Low Discharge Pressure 

Faulty Condenser Fan Control 

Check Fan Controls 

  

Suction Shut off partially closed 

Open Valve 

  

  

Adjust Water Regulating Valve or Water Supply 

  

  

See "Low Suction Pressure" below 

  

Insufficient Refrigerant Charge 

Check for leaks,  repair & recharge 

  

Low Ambient Conditions 

Check Condenser rating tables 

Low Suction Pressure 

Lack of Refrigerant 

Check for leaks,  repair,  & recharge. 

  

Clogged Liquid Line Filter Drier 

Replace 

  

Expansion Valve malfunction 

Check Superheat Setting,  adjust or replace. 

  

Condensing Temperature too low 

Check means of regulating Condensing Temperature 

  

Compressor will not unload 

See "Compressor will not unload" section below 

  

Insufficient Flow through evaporator 

Check circulation pump rotation and motor amperage. 

  

Not enough Glycol Concentration or Glycol 

  

Make sure Gate Valves on Evaporator inlet & outlet 

  

  

Level in Tank is too Low. 

  

are completely open.   

7-5 

  

  

Add required Glycol to System 

High Suction Pressure 

Excessive Load 

Reduce Load or add additional cooling equipment 

  

Expansion Valve malfunction 

Check Superheat of TXV,  replace if necessary 

Compressor will not unload 

Unloader mechanism defective 

Replace mechanism 

  

Faulty Thermostat or Pressure Control 

Check settings of device,  replace if necessary 

Oil Alarm 

Excessive Liquid Refrigerant in crankcase 

Check crankcase Heater.  Adjust TXV superheat. 

  

Oil Failure Control defective 

Replace 

  

Worn Oil Pump 

Replace Oil Pump. 

  

Stuck reversing gear on oil pump 

Reverse Rotation of Compressor 

  

Worn Bearings 

Replace Compressor 

  

Low Oil Level 

Check System for leaks,  repair,  & add Oil. 

  

Pump Housing Gasket leaks 

Replace Gasket 

Motor Overload Fault,  tripped Circuit 

Low Voltage during high load conditions 

Check for excessive voltage drop 

Breaker,  or Blown Fuses 

Grounded wiring in motor or power circuit 

Check wiring and repair fault. 

  

Loose power wiring 

Check wiring and tighten any loose connections 

  

High Condensing Pressure 

See corrective steps for "High Discharge Pressure" 

  

Voltage unbalance 

Check Power Supply.  Contact Power Company.  Do not 

  

High Ambient at bi-metal Overload Relay 

  

Operate until fault is corrected. 

  

  

  

Provide Ventilation to Motor Controls 

Compressor Thermal Switch Open 

Operating out of design conditions 

Add facilities to prevent system from operating out of  

  

Discharge Valve Partially closed 

  

design conditions. 

  

Blown Valve Plate Gasket 

Open 

  

Power Line Fault 

Replace Gasket 

  

  

  

Check Power Supply.  Contact Power Company.  Do not 

  

  

  

  

Operate until fault is corrected. 

Low Pressure Freeze Alarm 

Wrong Pump Rotation 

Reverse Rotation of circulation pump (CW from motor end) 

  

Evaporator Freeze Up 

Check Glycol Percentage.  Must be at least 20 F below 

  

Incorrect Freeze Point setpoint 

  

thermostat set point. 

  

  

  

Adjust freeze point for application,  consult factory. 

Summary of Contents for CHILSTAR Series

Page 1: ...Operations Manual...

Page 2: ...MPS 3 GLYCOL STORAGETANK 3 REFRIGERATION EQUIPMENT 3 SPIRAL DRUM EVAPORATOR 3 PUMPCURVESSUPPLIEDBYPUMPSERIES 4 INSTALLATION OPERATION MAINTENANCE 6 WIRING 7 MAINTENANCE iv PIPING 6 RECEIVING AND INSPE...

Page 3: ...report any damage Manufactured By Pro Refrigeration Inc Pro Refrigeration is located in Auburn WA Auburn is located 30 miles from Seattle WA in the shadow of Mt Rainier Physical Address 326 8th ST SW...

Page 4: ...CL CLASSIC NOTANK X NONE COMPRESSORMAKE B BITZER C CARLYLE M MANEUROP E EMERSON COPELAND X NONE P PROREFRIGERATION NUMBEROFREFRIGERATIONCIRCUITS 1 2 3 4 5 CIRCUITHORSEPOWER HERMETIC SEMI HERMETIC 02 1...

Page 5: ...g By manifolding the evaporators together we can maximize the efficiency of the heat exchanger surface area We offer a 5 year replace ment warranty for the evaporator The warranty does not cover failu...

Page 6: ...4 Pro Refrigeration Inc PUMP CURVES SUPPLIED BY PUMP SERIES 1ST Series Pump Curve 2ST Series Pump Curve...

Page 7: ...Packaged Glycol Chiller Systems 5 3ST Series Pump Curve 5SH Series Pump Curve...

Page 8: ...iping must be in accordance with applicable local and state codes 2 Refrigerant piping should be designed and installed in accordance with recommended practices outlined in ARI or ASHRAE piping guide...

Page 9: ...nd contaminants in the system not removed by proper evacuation can cause corrosion on compressor windings expansion valve freeze up oil sludge and high discharge pressures 2 Attach vacuum pump to low...

Page 10: ...possible loose or corroded wiring 6 Monitor system pressures daily and amperages monthly 7 Check system glycol tank level and percentage for proper freeze point The freeze point should be at least 20...

Page 11: ...l electrical codes it is likely an electrical disconnect safety switch will need to be located near the chiller system Check name plate or manual for electrical power supply requirements STEP 2 Open E...

Page 12: ...h the piping with water Visually check for any leaks on the system before proceeding STEP 5 Turn each circuit s STAGE switch to the ON position If your chiller is a single circuit system turn the CHIL...

Page 13: ...AGE CHILLER switches OFF and drain the water from system and tank If no tank is installed open up your piping inside the processing plant and drain water It is important to drain as much water as poss...

Page 14: ...pped inside the main electrical enclosure in a plastic bag Install these into the fuse block associated with your condensing unit If chiller has circuit breakers switch them to the ON position Danfoss...

Page 15: ...disconnect to to the ON position Turn CHILLER or STAGE switches to ON The chiller circulation pump should start running and compressors should stage on off according to the glycol setpoint temperatur...

Page 16: ...ipment purchased from Pro Refrigeration Inc Any materi als or equipment not manufactured by Pro Refrigeration Inc are only warranted in so much as warranted by the manufacturer or distributor of such...

Page 17: ...of our chillers must pass a stringent quality check list before being approved for shipment If a system is found to possess a workmanship flaw please call the factory and inform us of the defect which...

Page 18: ...Manual for Factory Settings High Pressure Cut Out Low Pressure Cut In Low Pressure Cut Out Oil Failure Control P29NC 3 FREEZE PROTECTION SETTINGS refer to Operation Manual for Factory Settings Low Pr...

Page 19: ...rocedures To order a refractometer glycol solution tester please contact your sales representative or contact the factory at the above listed phone number DESIRED GLYCOL GLYCOL FREEZE CONTROL CUT IN C...

Page 20: ...5 26 1 36 35 4 0 8 17 3 26 9 37 36 4 0 8 18 2 27 5 38 37 4 2 4 19 1 28 39 38 4 4 2 20 1 28 5 40 39 4 6 21 1 29 1 41 40 4 7 8 22 1 29 6 42 41 4 9 8 23 2 30 2 43 42 4 11 8 24 4 30 7 44 43 4 13 9 25 5 31...

Page 21: ...l Process Heat Exchanger Volume Capacity D Use chart 1 to find percentage concentration E Multiply total system volume by glycol percentage required Example Brewery Application with Fermenters as Proc...

Page 22: ...repair recharge B Clogged Liquid Line Filter Drier B Replace C Expansion Valve malfunction C Check Superheat Setting adjust or replace D Condensing Temperature too low D Check means of regulating Cond...

Page 23: ...arms Inspect for glycol leaks Refrigerant Sight Glass Inspection DAILY Daily Inspection Notes WEEKLY Date Date Suction Pressure Proper Glycol Reservoir Level Discharge Pressure Compressor Superheat We...

Page 24: ...Packaged Glycol Chiller Systems V NOTES...

Page 25: ...Pro Refrigeration Inc 326 8th ST SW Auburn WA 98001 Tel 800 845 7781 Fax 253 735 2631 Pro Refrigeration Inc 319 Farmington Road Mocksville NC 27028 Tel 800 845 7781 Fax 253 735 2631...

Reviews: