ROUTINE
MAINTENANCE
Filter Maintenance: The TRS21 is equipped with a 100-mesh
screen filter. This filter should be checked periodically. A partially
clogged filter will slow recovery rate.
Check filter cartridge as follows:
1. Use a 5/8" socket or boxed end wrench to remove IN port as
shown in Figure 1.
2. Remove suction port-filter cartridge as shown in Figure 2.
3. Clean cartridge or replace with new cartridge. (CPS #CRXF3)
4. Inspect 0-ring. Re-lubricate with compressor oil or equivalent
5. Place filter cartridge back into suction port fming.
6. Hand tighten this assembly back onto TRS21.
7. Use 5/8" socket or boxed end wrench to tighten 1/8 of a turn. Do
not over tighten; 0-ring damage may occur.
8. Check connection for leaks.
Piston Seal Maintenance: In cases of virgin refrigerant
recovery, it is recommended to add .25 ounce of refrigerant
oil to inlet port before each use.
WARRANTY
CPS41' Products, Inc. guarantees that all products are free of manufacturing and material defects to the
original owner for one year from date of purdlase. If equipment should fail during guarantee period it will
be repaired or replaced (at our option) at no charge. This guarantee does not apply to equipment that has
been altered, misused or solely in need of field service maintenance. All repaired equipment will carry an
independent 90 day warranty. This repair policy does not include equipment that is determined to be be
yond economical repair. WARRANTY DISCLAIP/ER: Use this device to recover only HVAC/R refrigerants from
sealed HVAC/R systems. WARRANTY VOIDED IF USED FOR ANY OTHER PmPOSE.