background image

Adjusting the Temperature Swing

The swing setting, often called 

CYCLE 

RATE, DIFFERENTIAL or ANTICIPATION 

is adjustable.  A smaller swing setting will 
cause more frequent cycles and a larger 
swing setting will cause fewer cycles.  
There are separate swing settings for heat 
and for cool.  Follow the steps below to 
adjust the 

SWING setting for heat or cool:

Room Temperature Calibration

This feature allows the installer to change 
the calibration of the room temperature 
display.  For example:  If the thermostat 
reads 70° and you would like it to read 
72° then 2.  You can adjust the 
room temperature display to ready -4°F 
to +4°F above or below the factory 
calibrated reading.  Follow the steps 
below to adjust the temperature reading:

Temperature swing, sometimes called differetial or cycle rate, can be customized for this 
individual application. For most applications choose a swing setting that is as long as possible 
without making the occupants uncomfortable.

PRO1 Tip

1.

2.

3.

4.

1.

2.

3.

4.

Select 

HEAT or COOL with the 

system switch.  

Hold down the            and            keys 
together for 3 seconds.

Use the            or             key to adjust 
the swing.  The swing is adjustable 
from ±02°F to ±20°F.  
For example:  A swing setting of 
05°F will turn the cooling on at 
approximately 0.5°F above the 
setpoint and turn the cooling off at 
approximately 0.5°F below the 
setpoint.  The factory default for 
cooling is 0.5°F and 0.4°F for heating.

Wait approximately 10 seconds for 
the thermostat to return to normal 
operation.

Select 

OFF with the 

system switch.

Hold down the            and          
keys together for 3 seconds.

Use the            or             key 
to adjust the room temperature 
display.

Wait approximately 10 seconds 
for the thermostat to return to 
normal operation.

Summary of Contents for T601-2

Page 1: ...01 2 U S Registered Trademark Patents pending Copyright 2010 Pro1 IAQ Inc All rights reserved Mounting and Battery Installation For assistance with this product please visit http www pro1iaq com or call Pro1 Customer Care toll free at 888 Pro1iaq 776 1427 during normal business hours Mon Fri 9 AM 6 PM Eastern Rev 1043 ...

Page 2: ......

Page 3: ...ermostat becomes inoperable Getting to know your thermostat LCD 1 2 Fan Switch 3 System Switch 4 Easy Change Battery Door 5 Setpoint Buttons 1 2 3 4 5 Low Battery Indicator Replace batteries when indicator is shown 1 will appear in the display when the auxiliary heat is active Indicates the current room temperature Displays the user selectable setpoint temperature System operation indicators ON wi...

Page 4: ...SUBBASE INSTALLATION ...

Page 5: ......

Page 6: ......

Page 7: ... delay ON or OFF with the jumper pin Reset button Delay The compressor delay will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on The cooling icon will flash during the delay period Select OFF or ON with the jumper pin as desired ...

Page 8: ...re swing sometimes called differetial or cycle rate can be customized for this individual application For most applications choose a swing setting that is as long as possible without making the occupants uncomfortable PRO1 Tip 1 2 3 4 1 2 3 4 Select HEAT or COOL with the system switch Hold down the and keys together for 3 seconds Use the or key to adjust the swing The swing is adjustable from 02 F...

Page 9: ...subbase 9 ...

Page 10: ...riday 9 AM 6 PM Eastern 41ºF to 95ºF 5ºC to 35ºC 44ºF to 90ºF 7ºC to 32ºC 1 amp per terminal 1 5 amp maximum all terminals combined 1ºF Heating is adjustable from 0 2ºF to 2 0ºF Cooling is adjustable from 0 2ºF to 2 0ºF 18 to 30 VAC NEC Class II 50 60 Hz for hardwire common wire Battery power from 2 AA Alkaline batteries 32º to 105º 0º to 41ºC 90 non condensing maximum 4 7 W x 4 4 H x 1 1 D ...

Reviews: