6
TECHNICIAN SETUP MENU
Note:
To lock the keypad hold down the and keys for 3
seconds. You will see a lock in the display. To unlock the keypad
hold down the and keys for 3 seconds.
Technician Setup Menu
This thermostat has a technician setup menu
for easy installer configuration. To set up the
thermostat for your particular application:
Configure the installer options as
desired using the table below.
Use the or keys to
change settings and the
NEXT STEP
or
PREV STEP key to move from one
option to another.
Note: Only press
DONE key when you want to exit the
Technician Setup options.
Press
MENU button
Press and hold
TECHNICIAN SETUP
button for 3 seconds. This 3 second delay
is designed so that homeowners do not
accidentally access the installer settings.
1.
2.
3.
This feature will
flash
FILT
in the
display after the
elapsed run time
to remind the
user to change the
filter. A setting of
OFF
will disable
this feature.
This feature allows
the installer to
change the
calibration of the
room temperature
display. For
example, if the
thermostat reads 70°
and you would like it
to read 72° then
2.
The compressor short
cycle delay protects
the compressor from
“short cycling”. This
feature will not allow
the compressor to be
turned on for 5
minutes after it was
last turned off.
The swing setting,
often called “cycle
rate”, “differential”
or “anticipation” is
adjustable. A smaller
swing setting will
cause more frequent
cycles and a larger
swing setting will
cause fewer cycles.
The swing setting,
often called “cycle
rate”, “differential”
or “anticipation” is
adjustable. A
smaller swing setting
will cause more
frequent cycles and a
larger swing setting
will cause fewer
cycles.
Keypad lockout
allows you to
configure the
thermostat so that
none or some of
the keys do not
function.
The heating swing
setting is adjustable
from ±0.4°F to
±2°F. For example:
A swing setting of
0.5°F will turn the
heating on at
approximately 0.5°F
below the setpoint
and turn the heating
off at approximately
0.5°F above the
setpoint.
Pick
PA
or
FU
PA
= partial keypad
lockout, which locks
all the keys except the
or keys.
FU
= Full keypad
lockout, which locks
out all the keys.
Note: Keypad lockout
instructions are below.
The cooling swing
setting is adjustable
from ±0.4°F to
±2°F. For example:
A swing setting of
0.5°F will turn the
cooling on at
approximately 0.5°F
above the setpoint
and turn the cooling
off at approximately
0.5°F below the
setpoint.
Selecting
ON
will not
allow the compressor
to be turned on for 5
minutes after the last
time the compressor
was on. Select
OFF
to remove this delay.
You can select the
minimum compressor
run time from “off”,
“3”, “4”, or “5”
minutes. If 3, 4, or 5
is selected, the
compressor will run
for at least the
selected time before
turning off.
You can adjust the
room temperature
display to ready -4°F
to +4°F above or
below the factory
calibrated reading.
You can adjust
the filter change
reminder from
OFF
to 2000
hours of runtime
in 50 hour
increments.
OFF
0 ºF
OFF
ON
0.5 ºF
0.4 ºF
NA
TECH SETUP
STEPS CONTINUED
ON THE NEXT PAGE
This feature allows the
installer to select the
minimum run time for
the compressor.
For example, a setting
of 4 will force the
compressor to run for
at least 4 minutes
every time the
compressor turns on,
regardless of the room
temperature.
Tech Setup Steps
Minimum
Compressor
On Time
Compressor
Short Cycle
Delay
Cooling
Swing
Heating
Swing
Keypad
Lockout
Room
Temperature
Calibration
Filter
Change
Reminder