Technical Data - Head Station 1A/1B/1C
Technical Data - Head Station 1A/1B/1C
Type differences (Hardware is identical with all types)
Head Station 1A
Head Station 1B
Head Station 1C
For all Head Stations
No ProfiTrace OE
ProfiTrace OE for 1 PROFIBUS n
ProfiTrace 2 live str OPC
(since June 2013)
ProfiTrace OE for 4 PROFIBUS ne
ProfiTrace 2 live str OPC
CommDTM
Backplane
Modules
Current available for the backplane
PROFIBUS networks
Compatible backplane units
32 (10 repeater modules positioned in the first 10 slots)
2.5 A
4
101-200012, 101-200023, 101-200024, 101-200027
Power supply specifications
Nominal supply voltage
Current consumption
Power
Reverse polarity protection
Redundant power supply
Wire diameter
10.8 .. 26.4 VDC
800 mA (fully loaded)
20 W
Yes
Yes
< 2.5 mm
2
Installation notes:
The device shall be supplied from an isolating transformer
having a secondary Listed fuse rated either:
•
Maximum 5 amps for voltages 12 .. 20 V, or
•
Maximum 4 amps for voltages 21 .. 24 V,
or is supplied by a Class 2 power supply, or equivalent.
Ethernet
Connector
Cable length
Link speed
MAC address
Supported protocols
Default IP address after reset/purchase
Connections
RJ-45
Max. 100 m
10 / 100 Mbps
9C.B2.06.xx.xx.xx (label on the side of the Head Station)
HTTP, FTP, SMTP, TELNET, DHCP, SNMP
192.168.1.254
20 simultaneous web server clients
Relay contact
Summary of Contents for ComBricks
Page 1: ...User Manual ...
Page 132: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 132 219 ...
Page 213: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 213 219 44 Certificates ...
Page 214: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 214 219 ...
Page 215: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 215 219 ...
Page 216: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 216 219 ...
Page 217: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 217 219 45 Notes ...
Page 218: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 218 219 ...