ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
185/219
Repeater Module
status
Data received
The idle voltage
when no node is
sending is
too low
Communication error
or bad telegrams
Repeater internal
failure
Signal amplitude
is
too low
Network 1: NW0 = L, NW1 = L
Network 2: NW0 =
R
, NW1 = L
Network 3: NW0 = L, NW1 =
R
Network 4: NW0 =
R
, NW1 =
R
Dipswitches or web
server settings
Redundancy for the
current network
Technical Data
–
RS-485-IS Barrier (101-201410)
NW0
NW1
LEFT
LEFT
RIGHT LEFT
LEFT
RIGHT
RIGHT RIGHT
RED
LEFT / RIGHT
H/S
LEFT / RIGHT
PROFIBUS Network
1
2
3
4
Redundancy
OFF / ON
Settings
Hardware / Software
ATEX (electrical)
Uo
Io
Ui
Li
Ci
Output characteristic
4.2 V
149 mA
≥ 4.2
≈ 0 μH V
Negligibly small
Linear
ATEX (compliance):
II (2) G [Ex ia Gb] IIC
EN-IEC60079-0: 2009 / EN-IEC60079-11: 2012 / EN-IEC60079-25: 2010
PROFIBUS International IS Installation Guidelines
Certification number:
DEKRA 12ATEX0192
LEDs
RDY
RX
HWE
ER
MIN
TERM
Module is ready for operation (ON)
Receiving telegrams (blinking)
Internal repeater error (contact PROCENTEC)
No or bad telegrams detected
Signal amplitude of the telegrams too low (< 1.64 V)
Idle voltage too low ( <0.35 V .. >0.75 V )
Alarm values can be changed through the web server.
Others
Head Station firmware
Operating temperature
Weight
MTBF
At least version 1.272
0 .. 60 °C
150 g
To be defined
Summary of Contents for ComBricks
Page 1: ...User Manual ...
Page 132: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 132 219 ...
Page 213: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 213 219 44 Certificates ...
Page 214: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 214 219 ...
Page 215: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 215 219 ...
Page 216: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 216 219 ...
Page 217: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 217 219 45 Notes ...
Page 218: ...ComBricks User Manual v6 4 0 January 18 PROCENTEC 218 219 ...