13.3
Quick Start checklist
This checklist lists all the steps to a quick usage of the PROFINET Device module as a Remote I/O station.
STEP 1:
Provide the Head Station 1B or 1C with the latest firmware, at least v1.272.
(
7
)
STEP 2:
Add at least two empty backplane slots to the ComBricks set.
STEP 3:
Use the rotary switch on the bottom to assign a custom or pre-defined
name to the PROFINET device.
STEP 5:
Insert the PROFINET Device module in one empty slot. Do not insert it in slot
number 11 or higher; this is not supported by the ComBricks.
(2.3)
STEP 6:
Insert a DI/DO/Relay card in the other empty slot.
(2.3)
STEP 7:
Provide power to the Head Station.
STEP 8:
Connect the Head Station to the Ethernet network with an Ethernet cable.
STEP 9:
Connect a PROFINET cable and connector to one of the RJ45 connectors.
STEP 10:
Check the Channel List (in web browser) to see if the modules appear.