Manual Mode / Test
In manual /Test mode the DG can start or stop by pressing Start and stop button
respectively. The main contactor can be switched on and off by pressing MCB
button and generator contactor can be switched on / off by pressing GCB button.
1.4
Engine solenoid Engine solenoid contact (Terminal 15 & 16) can be configured
in two modes
a. Mode 0: In this mode fuel solenoid contact changes from NO to close at
the time of cranking and remains close till the Genset is running. For
stopping the Generator this contact opens.
b. Mode 1: In this mode fuel solenoid contact remains open at the time of
cranking and till the Genset is running . For stopping the Generator this
contact closes for a user programmed time.
For changing the solenoid mode first press Reset button, than simultaneously
press GCB button . It’s a good practice to switch off and than switch on the
battery supply after changing the mode.
1.5
Display
α)
It LCD display, to display voltages. Beside the numeric display there are 14 LEDs
for annunciations
1.6
Programming mode
Programming mode can be entered any time by simultaneously pressing Reset & A/M
keys. The following table details the various programmable parameters:
1.6.1
Setting table
Sl.
No
Parameter
Explanation of parameter
Default
setting
Setting
Range
1
Mains Over
Voltage
Max. permissible voltage, above this the
voltage is treated unhealthy & Genset is
started.
270V
80-300V
2
Mains Under
Voltage
Min. permissible voltage, below this the
voltage is treated unhealthy & Genset is
started
180V
80-300V
3
Mains voltage
supervision time
Time for which the mains voltage has to be
unhealthy (Under or Over voltage as
defined above in 1 & 2) before starting the
Generator.
10Sec
0-999Sec
4
Generator Start
Delay
After opening the Mains MCB, Generator
starting is delayed by generator start delay
time
Disable
0-
999Sec.
5
Generator Over
Voltage
Max. permissible voltage, above this the
voltage is treated unhealthy & the
Generator is stopped by releasing fuel
solenoid.
Generator contactor is released and mains
contactor is closed. Hooter shall be
activated .
270V
80-300V
6
Generator Under
Voltage
Min. permissible voltage, below this the
voltage is treated unhealthy & the
180V
80-300V
Cat/DCG-6D1I/07-08/03/Ver 1 Page 6/10