Controller options 

 

 

 

Operation Modes 

HLS34 has two operation modes: DAY and NIGHT. The unit can be switched between day and night modes 
either via Modbus network or via the DAY EXTENSION typically connected to PIR. The user can also 
change NIGHT mode to DAY mode by pressing “MAN IN THE HOUSE” (occupancy) button on the unit. After 
2-hours (adjustable) DAY mode returns automatically back to the NIGHT  mode. When in DAY mode the 
controller operates the valve outputs according to the below diagram. 
 
DAY MODE 
 
In the DAY mode the temperature is controlled to the setpoint using PI-control. The controller has adjustable 
dead zone between heating and cooling modes. 
 
The controller DAY setpoint (SP) is calc ulated as follows:- 
 
SP = SP

network

 

±

  SP

local

, where SP

network

 is setpoint set via Modbus network and SP

local

 is the setpoint set by 

the user by pressing “+” and “-“ buttons. SP

local

 range is limited at the commissioning stage (default 

±

3°C) 

 
In the NIGHT mode the controller controls to the NIGHT/FROST setpoint. If the temperature falls below the 
NIGHT setpoint (5..20°C), the heating output is opened and the fan is overridden on (if fan speed control has 
been enabled). The NIGHT setpoint is adjustable via Modbus network or in the configuration mode. 
 
When the controller returns to the DAY MODE from NIGHT, the controller DAY setpoint can return to the 
DAY setpoint programmed previous day, or the DAY SP can be reset to the  SP

network

 Modbus Network 

Setpoint. This is a configurable option (configuration parameter SP_ND). If no network setpoint is available 
21°C is used as default.   
 

 

 

 

Air-side application 
Description of operation 

 

 

Summary of Contents for HLS34

Page 1: ...egral Action Time Tn 50 500s factory default 300 sec 3 Point Control Actuator Runtime Mt 30 300s factory default 180 sec Protection Class IP20 Operating Humidity 0 95 rH non condensing Wiring Terminals 1 5 mm2 Housing ABS Plastics Dimensions 87W x 86H x 32D mm The HLS34 is specifically designed for individual room temperature and zone control applications The controllers have built in RS 485 chann...

Page 2: ...oducts meet the requirements of directive 89 336 EEC and standards EN50081 1 1992 Emission and EN50082 2 1995 Immunity Wiring Terminals The electrical installation device connection and commissioning can only be carried out by qualified professionals and according to the local wiring regulations AIR SIDE APPLICATION WIRING ...

Page 3: ...ol The controller has adjustable dead zone between heating and cooling modes The controller DAY setpoint SP is calc ulated as follows SP SPnetwork SPlocal where SPnetwork is setpoint set via Modbus network and SPlocal is the setpoint set by the user by pressing and buttons SPlocal range is limited at the commissioning stage default 3 C In the NIGHT mode the controller controls to the NIGHT FROST s...

Page 4: ...CO2 transmitter is connected to the controller analogue input U1 the controller can be enabled to boost the fan speed switch the fan On in case of high CO2 content in the occupancy space This is a very useful feature to provide demand based ventilation High CO2 level overrides the fan speed set by the temperature based fan speed control Day Extension via digital input The controller has hardware d...

Page 5: ...ol The HLS34 handheld tool allows quick configuration of large number of controllers To configure the controller locally first remove the top cover A CONFIGURATION MODE JUMPER is located below the LCD display When the jumper is set the controller is in normal operation By removing the jumper the controller enters to the configuration mode Once the configuration has been completed by setting the ju...

Page 6: ...1 1 1992 Emission and EN50082 2 1995 Immunity Network Diagram Up to 128 HLS34 controllers can be connected to a single network segment The diagram below illustrated the typical installation where the room controllers are connected on the floor level to the Netbiter embedded web server Each Netbiter holds a time schedule for the floor to switch the controller between day and night operation modes ...

Page 7: ...y Occupied NIGHT mode to DAY mode Bit1 On Off 3 DAY EXTENSION NIGHT mode to DAY mode Bit2 On Off 4 EXT S External Sensor Bit3 On Off 5 Fan Speed 1 run Bit4 On Off 6 Fan Speed 2 run Bit5 On Off 7 Fan Speed 3 run Bit6 On Off FUNCTION CODE 03 READ HOLDING REGISTERS 2 Coils 16 01 16 bit 3 Fan Speed Set by Network Signed 16 0 1 2 3 4 4 Cooling Output Set by Network Signed 16 0 0 100 0 5 Heating Output ...

Page 8: ... Off 7 Fan Speed 3 asked Bit6 On Off 8 Fan Speed 4 Auto asked Bit7 On Off FUNCTION CODE 06 WRITE SINGLE REGISTER 2 Coils 16 01 16 bit 3 Set Fan Speed Signed 16 0 1 2 3 4 4 Cooling Output Overdrive mode on Signed 16 0 0 100 0 5 Heating Output Overdrive mode on Signed 16 0 0 100 0 6 Set Point by Network DAY value only Signed 16 5 0 37 0 C 13 DAY EXTENSION period Signed 16 1 480 min FUNCTION CODE 16 ...

Reviews: