background image

 

 

 

1150.11E 

 January 2007 

 

 

 

www.produal.fi

 

 

Enquiries: T: 

05 230 9200

   F: 

05 230 9210

    

Copyright 

 2005 Produal Oy. All rights reserved 

Products meet the requirements of directive 89/336/EEC and standards EN50081-1: 1992 (Emission) and EN50082-2: 1995 (Immunity). 

 

 

 

NIGHT MODE 
 
The configuration parameter J7 sets the controller operation during the night time; Relaxed Deadzone or 
Frost Protection (Thermostat). 
 
1) Relaxed Deadzone at Night 
 
The controller operates as in the DAY mode but the deadzone around the controller is expanded to NDz 
value. Therefore at the night time the controller energy consumption is reduced. 
 
NOTE: It is also possible to set the night deadzone to smaller value than day deadzone. 
 
2) Frost Protection (Thermostat) 
 
In the NIGHT mode the controller controls to the NIGHT/FROST setpoint. If the temperature falls below the 
NIGHT setpoint (5..20°C), the heating valve is opened and the fan is overridden on (if fan speed control has 
been enabled). The NIGHT setpoint is adjustable via Modbus network or in the configuration mode. If the 
temperature exceeds 2°C the NIGHT setpoint the heating valve is closed and the fan is switched off. 

 

 

Fan Speed Control 

Fan speed control can be enabled during the commissioning (configuration parameter FAN). When fan 
speed control is enabled the Heating Analogue output is converted operate as the control signal to the 
FCRY3 fan speed control relay module.  
 
In automatic control the fan speed output operates as follows:- 

Valves closed 

à

 Fan speed output 0% 

Heating/Cooling Valve Opens 

à

 Fan speed output is set to 3.3V (Speed 1) 

Heating/Cooling Valve Opens more than 25% 

à

  speed output is set to 6.6V (Speed 2) 

Heating/Cooling Valve Opens more than 50% 

à

  speed output is set to 10V (Speed 3) 

 
Automatic Speed 3 control is disabled as default. However, the user can manually override speed 3 on 
through the keypad. Typically speed 3 causes a higher level fan noise and therefore it is recommended that 
this is manual override option operated by the user. Automatic Speed 3 control can be enabled during the 
commissioning via basic settings. 
 
When the controller switches to NIGHT mode or the temperature is within the dead zone, the fan is 
automatically switched OFF after 5 minutes timeout. 

 

 

Ventilation Boost 
(CO2 Control) 

If HDK or HDH CO2 transmitter is connected to the controller analogue input U1, the controller can be 
enabled to boost the fan speed / switch the fan On in case of high CO2 content in the occupancy space. This 
is a very useful feature to provide demand based ventilation. High CO2 level overrides the fan speed set by 
the temperature based fan speed control. 

 

 

Day Extension via digital
input 

The controller has hardware digital input that can be connected to a momentary push button contact (e.g. 
PJP1) or to a PIR sensor (e.g. LA24) to override the controller to DAY operation. These are ty pically used 
out of hours to provide comfort control. Alternatively PIR input can be used as the primary means of 
switching between DAY and NIGHT modes. The digital input is normally closed. 
 
NOTE: The digital input is activated when it is first time closed. The controller is supplied with the digital input 
as open contact. 

 

 

Day Extension via  
keypad 

The controller can be overridden to DAY operation by pressing the “MAN IN THE HOUSE” occupancy 
button. When pressed the controller is overridden to DAY mode for the period of two hours. The extension 
time is adjustable between 1..480 minutes via Modbus network. 

 

 

VAV Control with Fresh 
Air Demand Boost 

The controller can also be used as Variable Air Volume controller by connecting the VAV Box damper to the 
output Y1. The output Y1 is then modulated according to temperature demand in the room space.  
 
If HDK or HDH CO2 transmitter is connected to the controller analogue input U1, the controller can increase 
the fresh air demand i.e. overdrive the analogue output Y1 when the CO2 content in the room space 
exceeds the acceptable limit. The CO2 influence is set via configuration parameters CO2 LO (e.g. 750 ppm) 
and CO2 HI (e.g. 1250 ppm). Between the CO2 limits the influence is calculated using linear relationship i.e. 
when CO2 measurement is at CO2 HI setpoint, the CO2 influence is 100% (Y1=10V). 

 

 

Air-side application 

Air side application controls the temperature by modulating the damper output and 3-point control outputs. 
When the room temperature is at the setpoint the control output is at 50%. When the temperature increases 
above the setpoint the control signal starts to drop providing cooling to the room space. When the 
temperature drops below the setpoint the control output increases to provide heating to the room space. 
 
For the air-side application to operate correctly set configuration parameters J1 and J2 to Direct Operation. 

 

Summary of Contents for HLS34

Page 1: ...egral Action Time Tn 50 500s factory default 300 sec 3 Point Control Actuator Runtime Mt 30 300s factory default 180 sec Protection Class IP20 Operating Humidity 0 95 rH non condensing Wiring Terminals 1 5 mm2 Housing ABS Plastics Dimensions 87W x 86H x 32D mm The HLS34 is specifically designed for individual room temperature and zone control applications The controllers have built in RS 485 chann...

Page 2: ...oducts meet the requirements of directive 89 336 EEC and standards EN50081 1 1992 Emission and EN50082 2 1995 Immunity Wiring Terminals The electrical installation device connection and commissioning can only be carried out by qualified professionals and according to the local wiring regulations AIR SIDE APPLICATION WIRING ...

Page 3: ...ol The controller has adjustable dead zone between heating and cooling modes The controller DAY setpoint SP is calc ulated as follows SP SPnetwork SPlocal where SPnetwork is setpoint set via Modbus network and SPlocal is the setpoint set by the user by pressing and buttons SPlocal range is limited at the commissioning stage default 3 C In the NIGHT mode the controller controls to the NIGHT FROST s...

Page 4: ...CO2 transmitter is connected to the controller analogue input U1 the controller can be enabled to boost the fan speed switch the fan On in case of high CO2 content in the occupancy space This is a very useful feature to provide demand based ventilation High CO2 level overrides the fan speed set by the temperature based fan speed control Day Extension via digital input The controller has hardware d...

Page 5: ...ol The HLS34 handheld tool allows quick configuration of large number of controllers To configure the controller locally first remove the top cover A CONFIGURATION MODE JUMPER is located below the LCD display When the jumper is set the controller is in normal operation By removing the jumper the controller enters to the configuration mode Once the configuration has been completed by setting the ju...

Page 6: ...1 1 1992 Emission and EN50082 2 1995 Immunity Network Diagram Up to 128 HLS34 controllers can be connected to a single network segment The diagram below illustrated the typical installation where the room controllers are connected on the floor level to the Netbiter embedded web server Each Netbiter holds a time schedule for the floor to switch the controller between day and night operation modes ...

Page 7: ...y Occupied NIGHT mode to DAY mode Bit1 On Off 3 DAY EXTENSION NIGHT mode to DAY mode Bit2 On Off 4 EXT S External Sensor Bit3 On Off 5 Fan Speed 1 run Bit4 On Off 6 Fan Speed 2 run Bit5 On Off 7 Fan Speed 3 run Bit6 On Off FUNCTION CODE 03 READ HOLDING REGISTERS 2 Coils 16 01 16 bit 3 Fan Speed Set by Network Signed 16 0 1 2 3 4 4 Cooling Output Set by Network Signed 16 0 0 100 0 5 Heating Output ...

Page 8: ... Off 7 Fan Speed 3 asked Bit6 On Off 8 Fan Speed 4 Auto asked Bit7 On Off FUNCTION CODE 06 WRITE SINGLE REGISTER 2 Coils 16 01 16 bit 3 Set Fan Speed Signed 16 0 1 2 3 4 4 Cooling Output Overdrive mode on Signed 16 0 0 100 0 5 Heating Output Overdrive mode on Signed 16 0 0 100 0 6 Set Point by Network DAY value only Signed 16 5 0 37 0 C 13 DAY EXTENSION period Signed 16 1 480 min FUNCTION CODE 16 ...

Reviews: