Direct spraying of water on the exchanger is prohibited. When the
ramps are mounted on site, the nozzles must be oriented outwards at an
angle of 45 °, cf. diagram beside.
6-
TROUBLESHOOTING
les of faults
FAULT
PROBABLE CAUSE
ACTION REQUIRED
Condensing Pressure too high
Insufficient air flow into condenser.
Clean condenser.
Check fan motors.
Installation overcharged with fluid.
Drain liquid into reservoir.
Air or non-condensable gas in the HP circuit.
Purge
Condensing Pressure too low
Fan cut-in incorrectly set.
Adjust pressure switch.
Fans not working
Motor out of order.
Replace
Main power lower than acceptable range.
Check current values with a voltmeter.
Phase missing.
Measure current between phase and
motor terminal block.