background image

 

1

  

 

 

 

 

 

 

 

   INSTRUCTION  
       MANUAL 

 
 
 

INDICE 

 
Sec. 

THEME 

Page 

1. 

FUNCIONAL DESCRIPCION 

2. 

TECHNICAL CARACTHERISTICS  

3. 

INSTALLATION 

3.1. 

Wall mounting 

3.2. 

Connections 

3.3. 

Inputs 

3.4. 

Activation by external order 

3.5. 

Outlets 

3.6. 

Supplementary relays 

3.7. 

Option with preheating 

3.8. 

Option for petrol engines 

3.9. 

Option 

start-up 

of 

electric 

generator for net failure detection 

 

3.10. 

Miscellaneous notes 

4. 

BREAKDOWN GUIDE 

5. 

CONNECTION 

SCHEME 

OF 

MISCELLANEOUS OPTIONS 

 
 

PRESENTATION 

We wish to express our thanks for the confidence 

in us which you have demonstrated by your interest in 
our purchase of the DIESEL-CONTROL 100. 

For us, this confidence inspires us to work harder 

every day to deserve it, and thus, to justify the tradition 
of quality which our products have. 

This manual will allow you to see the capacity of 

the unit as well as its installation and use. 

However, if any doubts should remain, let us know 

and we will happy attend to them. 

1. FUNCIONAL DESCRIPTION 

This  is  an  electronic  unit  for  the  automatic 

starting  and  stopping  of  diesel  and  petrol  engines, 
with breakdown detection. 

 

STARTING 

Starting can be carried out: 
a)  By means of a programmable clock which 

can be built into the unit. 

b)  By  signals  from  external  elements  (level 

sensors, another programmer, etc.). 

c)  Manually ( “MANUAL START” button). 
The activation time of the starter motor can be 

adjusted  between  1  and  12  seconds  (“START” 
button). 

In case of a failure in the starting, the unit will 

make up to 4 attempts, with 2 minute pauses between 
them.  If  all  attempts  fail,  there  is  an  illuminated 
indicator  which  warns  of  the  occurrence  (“START 
FAIL”). 

The unit will detect the starter failure by means 

of the oil pressure. 

There is a illuminated warning light for engine 

working order (“WORKING”). 

STARTER FUNCTIONING THEORY 

On receiving a start order, be it from the builtin 

clock, the manual start or external elements, the unit 
activates the starter relay for the prefixed time set by 
the  corresponding  adjustment. On finishing, it waits 
for 1 and a half minutes to detect the working of the 
engine through the oil pressure. 

If it has failed to start, it will carry out up to 4 

attempts, separated by a fixed timing of two minutes. 

If all these attempts fail to start the engine, the 

“START FAIL” indicator will be activated 

The contact relay and the “WORKING” indicator 

remain activated from start to stop. 

If the engine is working and the pressure gauge 

input is disconnected, the unit not obey start orders. 

There  is  a  CONTACT  outlet  which  remains 

Summary of Contents for diesel controll 100

Page 1: ...f a programmable clock which can be built into the unit b By signals from external elements level sensors another programmer etc c Manually MANUAL START button The activation time of the starter motor...

Page 2: ...the unit will automatically activate the stop relay also keeping the SENSOR BREAKDOWN indicator lit although the breakdown disappears This will only go out on restarting engine again However if the b...

Page 3: ...NG BOX Metal with lock 25x25x8 3 INSTALLATION 3 1 WALL MOUNTING 4 pieces for wall mounting are supplied with the unit which are mounted from the outside and without need to open the unit in the holes...

Page 4: ...r with a similar wire There are engines which need to work with double injection by way of a small electro magnet which will be connected in parallel with the starter The stop outlet terminal 3 can ac...

Page 5: ...positive to the pole of the winding 3 7 OPTION WITH PREHEATING The units delivered with this option incorporate another button on the frontpiece where the timing in seconds of the preheating to be car...

Page 6: ...ted and the WORKING LED does not light up CAUSES Mistaken polarity in the supply The oil pressure gauge is not connected to terminal 5 The oil pressure gauge is defective or does not indicate mass wit...

Page 7: ...7 5 CONNECTION SCHEME OF MISCELLANEOUS OPTIONS Delay option in the pump input Option of 2 irrigation sector with delay in the input pump...

Page 8: ...8 Option of irrigation plus fertiliser with delay in the input pump...