12

 

6. Trouble Shooting 

If the UPS system does not operate correctly, please attempt to solve the problem using 
the table below. 

 

Problem 

Possible cause 

Remedy 

No indication, no warning tone even 

though system is connected to 

mains power supply 

No input voltage 

Check  building  wiring  socket  outlet 

and input cable. 

LINE LED blinks 

Phase and neutral 

conductor at input of 

UPS system are 

reversed 

Rotate mains power socket by 180° or 

connect UPS system. 

LINE-LED blinks and 

BATTERY-LED lights up 

Input power and/or 

frequency are out of 

tolerance 

Check input power source and inform 

dealer if necessary 

LINE and BYPASS LED light up 

even though the power supply is 

available 

Inverter not switched on  Press On-Switch “I” 

INVERTER LED lights up, and 

audible alarm sounding every 1 

beep in every 4 seconds 

Mains power supply 

has failed 

Switching to battery mode 

automatically. When audible alarm 

sounding every second, battery is 

almost empty. 

FAULT LED lights, warning tone 

once a second 

Overload 

Remove loads of UPS output. 

FAULT-LED lights up, permanent 

warning tone 

UPS fault 

Notify dealer!! 

Emergency supply period shorter 

than nominal value 

Batteries not fully 

charged / batteries 

defect 

Charge the batteries for at least   

1 - 2 hours and then check capacity. If 

the problem still persists, consult your 

dealer. 

FAULT LED lights, BATTERY-LED 

blinks, warning tone once a second   

Charger or Batteries 

damaged 

Notify dealer!! 

 

Please have the following information at hand before calling the After-Sales Service 
Department: 

1. Model number, serial number 
2. Date on which the problem occurred 
3. Detailed description of the problem 

Summary of Contents for UPS T1000

Page 1: ...USER MANUAL ON LINE UPS UPS T1000 2000 3000 Uninterruptible Power Supply www pinnacle co za...

Page 2: ...D OPERATION 6 TROUBLE SHOOTING 7 MAINTENANCE 7 1 OPERATION 7 2 STORAGE 8 TECHNICAL DATA 8 1 ELECTRICAL SPECIFICATIONS 8 2 OPERATING ENVIRONMENT 8 3 TYPICAL STORED ENERGY TIME TYPICAL VALUES AT 25 C IN...

Page 3: ...13 SOFTWARE FREE SOFTWARE DOWNLOAD WINPOWER APPENDIX 1 BACK PANEL...

Page 4: ...s are earthed by the input power cord please insert the power cord into mains socket before using of UPS Connect the UPS only to an earthed shockproof socket outlet The building wiring socket outlet s...

Page 5: ...that no voltage is present before servicing Batteries have a high short circuit current and pose a risk of shock Take all precautionary measures specified below and any other measures necessary when...

Page 6: ...nt IEC EN 61000 3 2 Input Current 16A Voltage Fluctuation and Flicker IEC EN 61000 3 3 Input Current 16A EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE...

Page 7: ...commonly used notations Some or all of the following Notations may be used in this manual and may appear in your application process Therefore all users should be familiar with them and understand th...

Page 8: ...he inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by the mains voltage I...

Page 9: ...t LINE LED blinks when the phase and neutral conductor have been reversed at the input of the UPS system If LINE LED and BATTERY LED light up the mains power supply is out of tolerance BATTERY LED The...

Page 10: ...the UPS system if the mains power is available normal operation 2nd LED 96 105 3rd LED 76 95 4th LED 56 75 5th LED 36 55 6th LED 0 35 In the battery operation the LEDs indicate the capacity of the bat...

Page 11: ...PS T3000 S 2 2 UPS Output Connection The output of UPS T1000 S and UPS T2000S Non CE are socket types only Simply plug the load power cord to the output sockets to complete connection Model No Output...

Page 12: ...on the UPS Then the UPS will get into self test status first After having finishing the self test the UPS will get into the inverter mode at this time the Utility Power LED Inverter LED and Load and B...

Page 13: ...on 8 Operation Procedure of External Battery for Long Backup time Model S Model The units with CE markings 1 Use the battery pack with voltage 36VDC for 1KS 3 pcs of 12V batteries 96VDC for UPS T2000S...

Page 14: ...the battery The black wire is connected to the terminal of the battery Note the green yellow wire is grounded for protection purpose 7 Do not connect the UPS to any load yet Then connect the power cor...

Page 15: ...Switch I INVERTER LED lights up and audible alarm sounding every 1 beep in every 4 seconds Mains power supply has failed Switching to battery mode automatically When audible alarm sounding every seco...

Page 16: ...ient temperature has been exceeded the batteries must be replaced In this case please contact your dealer 7 2 Storage If the batteries are stored in temperate climatic zones they should be charged eve...

Page 17: ...1kW Voltage 220 230 240 1 2 VAC Frequency 50 1 0 2 Hz Battery mode Wave form sinusoidal BATTERIES Model No UPS T1000 UPS T2000 UPS T3000 Number and type 3 12V 7 2Ah 8 12V 7 2Ah 8 12V 7 2Ah 8 2 Operat...

Page 18: ...and weights Model No Dimensions W x D x H mm Net Weight kg UPS T1000 145X400X220 14 UPS T1000S 145X400X220 7 UPS T2000 192X460X340 34 5 UPS T2000S 192X460X340 15 UPS T3000 192X460X340 35 5 UPS T3000S...

Page 19: ...gions of hot climates the battery should be charged and discharged every 2 months The standard charging time should be at least 12 hours Under normal conditions the battery life lasts 3 to 5 years In...

Page 20: ...de otherwise it may result in electric shock or fire 6 Make sure that there is no voltage before touching the batteries The battery circuit is not isolated from the input potential circuit There may b...

Page 21: ...he generator Activate the generator and wait until the operation is stable before supplying power of the generator to the UPS be sure that the UPS is in idle mode Then turn on the UPS according to the...

Page 22: ...own in the following diagram Fig 15 3 The utility power LED and the bypass LED are lit The displayed number of the load LEDs will be turned on in accordance with the load capacity connected The UPS wi...

Page 23: ...s series UPS has AS400 card an optional accessory for AS400 communication protocol Please contact your local distributor for details The following is the pin assignment and description of DB 9 connect...

Page 24: ...ny UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Go to the website http www ups software download com winpower htm 2 Choose the operation system you need and follow the...

Page 25: ...Appendix 1 Back Panel Back View of UPS T1000 S Back View of UPS T2000 S Non CE certified Back View of UPS T2000S CE certified UPS T2000 CE certified...

Page 26: ...Back View of UPS T3000 S Non CE certified Back View of UPS T3000 S CE certified...

Page 27: ...614 00279 01...

Reviews: