3-4-3. Connect devices to UPS 

After the UPS is turned on, you can connect devices to the UPS. 
1)    Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total 

load level.   

2)  If it is necessary to connect the inductive loads such as a printer, the in-rush current should be 

calculated carefully to see if it meets the capacity of the UPS, because the power consumption of 

this kind of loads is too big. 

3)  If the UPS is overload, the buzzer will beep twice every second. 
4)  When the UPS is overload, please remove some loads immediately. It is recommended to have the 

total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload 

for system safety.   

5)  If the overload time is longer  than  acceptable time listed in spec at AC mode, the UPS will 

automatically transfer to Bypass mode.    After the overload is removed, it will return to AC mode. If 

the overload time is longer  than  acceptable time listed in spec at Battery mode, the UPS will 

become fault status. At this time, if bypass is enabled and the voltage and frequency in the range of 

it is set value, the UPS will power to the load via bypass. If bypass function is disabled or the input 

power is not within bypass acceptable range, it will cut off output directly. 

3-4-4. Charge the batteries 

1)  After the UPS is connected to the utility power and working on the AC mode, the charger will charge 

the batteries automatically except in Battery mode or during battery self-test.   

2)  Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be 

shorter than expected time. 

3-4-5. Battery mode operation 

1)  When the UPS is in Battery mode, the buzzer will beep according to different battery capacity. If the 

battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery 

voltage drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that 

the battery is at low level and the UPS will shut down automatically soon. Users could switch off 

some non-critical loads to disable the shutdown alarm and prolong the backup time. If there is no 

more load to be switched off at that time, you have to shut down all loads as soon as possible to 

protect the devices or save data. Otherwise, there is a risk of data loss or load failure.   

2)  In Battery mode, if buzzer sound annoys, users can press the Mute button to disable the buzzer. 
3)  The backup time of the long-run model depends on the external battery capacity. 
4)  The backup time may vary from different environment temperature and load type. 
5)  When setting backup time for 16.5 hours (990min in LCD setting menu 09), after discharging 16.5 

hours, UPS will shut down automatically to protect the battery. This battery discharge protection 

can be enabled or disabled through LCD panel control. (Refer to 3-7 LCD setting section) 

3-4-6. Test the batteries 

1)    If you need to check the battery status when the UPS is running in AC mode/CVCF mode/ECO mode, 

you could press the “Test” button to let the UPS do battery self-test. 

2)  To keep the system reliable, the UPS can perform the battery self-test periodically while connect the 

monitoring software. 

3)  Users also can set battery self-test through monitoring software. 
4)  If the UPS is at battery self-test, the LCD display and buzzer indication will be the same as at 

Summary of Contents for 10KRT

Page 1: ...ONLINE UPS User Manual MASTER II SERIES 1P 1P RACK TOWER PRO800 QRS QRL 6KVA 10KVA Version 1 00 English...

Page 2: ...LE UPS INSTALLATION 7 2 5 UPS INSTALLATION FOR PARALLEL SYSTEM 9 2 6 SOFTWARE INSTALLATION 11 3 OPERATIONS 12 3 1 BUTTON OPERATION 12 3 2 LED INDICATORS AND LCD PANEL 12 3 3 AUDIBLE ALARM 14 3 4 SINGL...

Page 3: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Page 4: ...ed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary power switches installed in places away from the device to alert the electrical mainte...

Page 5: ...its own internal current source batteries The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fu...

Page 6: ...owing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option On...

Page 7: ...available for parallel model 3 External battery connector 4 Intelligent slot 5 RS 232 communication port 6 USB communication port 7 Emergency power off function connector EPO connector 8 Input circuit...

Page 8: ...module in 2U Assemble two feet and one short extension as one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module in the stands as shown in step 3 S...

Page 9: ...c shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and d...

Page 10: ...ld only connect to its supplied external battery pack The battery type and voltage may be different If you connect them together it maybe causes the hazard of electric shock or fire Warning Only for l...

Page 11: ...or Parallel System If the UPS is only available for single operation you may skip this section to the next 1 Install and wires the UPSs according to the section 2 3 2 Connect the output wires of each...

Page 12: ...10 Diagram 2 Wiring diagram of parallel system for tower model Diagram 3 Power cable connection for RT model Diagram 4 Wiring diagram of parallel system for RT model...

Page 13: ...11 2 6 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown...

Page 14: ...s button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press...

Page 15: ...y voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Page 16: ...operates in Bypass mode and supplies power to the loads via the bypass NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on the input breaker In Bypa...

Page 17: ...up time may be shorter than expected time 3 4 5 Battery mode operation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more th...

Page 18: ...it means that there are some problems for UPS operation Users can get the warning code from LCD panel Please check the 3 11 warning code table and the trouble shooting table in chapter 4 for details...

Page 19: ...e error between real output voltage and detected value of UPS is less than 1V 3 Turn off each UPS Refer to section 3 4 7 Then follow the wiring procedure in section 2 4 4 Remove the cover of parallel...

Page 20: ...le Then remove the unit from the parallel system Second method 1 If the bypass is abnormal you can not remove the UPS without interruption You must cut off the load and shut down the system 2 Make sur...

Page 21: ...to set up the UPS Refer to following diagram Programs available list for parameter 1 Code Description Bypass No output AC ECO CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Vol...

Page 22: ...60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output frequency will...

Page 23: ...range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose following two options DIS disab...

Page 24: ...ng Interface Setting Parameter 3 000 999 Set the maximum backup time from 0min to 999min UPS will shut down to protect battery after backup time arrives DIS Disable battery discharge protection and ba...

Page 25: ...ld be suitable to battery specifications 15 Inverter voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter voltage Parameter 3 the voltage range is from 0V to 6...

Page 26: ...se set up calibrated current as 3 Setting charging current 4A real measured current 3 7A 0 3A 3 8 Operating Mode Status Description If parallel UPS systems are successfully set up it will show one mor...

Page 27: ...lay Bypass mode Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes LCD display Battery Test De...

Page 28: ...PS 12V abnormal 6E None 3 10 Warning Indicator Warning Icon flashing Alarm Battery low Beeping every second Overload Beeping twice every second Battery unconnected Beeping every second Over charge Bee...

Page 29: ...ads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes fault Then UP...

Page 30: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Page 31: ...A 10 max 4 A 10 max 1 A 10 max 4 A 10 max Charging Voltage Battery number 13 65 V 1 PHYSICAL Dimension DXWXH mm UPS Unit 600 x 438 x 88 2U Battery Pack 688 x 438 x 88 2U UPS Unit 600 x 438 x 88 2U UPS...

Page 32: ...ERS INDONESIA Office PT PROLiNK INTIDATA NUSANTARA Walk In Jl Cideng Barat No 79 Jakarta Pusat 10150 Indonesia Email Support support id prolink2u com MALAYSIA Office FIDA SYSTEMS M SDN BHD Walk In 29...

Reviews: