5)

 

For example, you want to have charging current in 4A, but in fact, the charging current is measured 

only 3.7A. Then, you need to select “+” and change the number to 4 in parameter 3. It means the 

setting charging current will be added 0.3A as output charging current. Then, confirm this 

modification by pressing “ON/Enter” button. Now, you may press “Test/UP”  and  “Mute/Down” 

buttons at the same time to exit the setting mode. 

NOTE 1: 

Be careful that the maximum charging current should not exceed the maximum  battery 

charging current. 

NOTE 2

:

 

All parameter settings will be saved only when UPS shuts down normally with internal or 

external battery connection.  (Normal UPS shutdown means turning off input breaker in bypass/no 

output mode). 
 

3-5. Parallel Operation 

3-5-1. Parallel system initial startup 

First of all, please make sure all of the UPSs are parallel models and have the same configuration. 
1)    Turn on each UPS to AC mode respectively (Refer to section 3-4-1). Then, measure the output 

voltage of each UPS to check if the voltage difference between actual output and setting value is 

less than 1.5V (typical 1V) with multimeter. If the difference is more than 1.5V, please calibrate the 

voltage by configuring inverter voltage adjustment (Refer to Program 15, section 3-7) in LCD 

setting. If voltage difference remains more than 1.5V after calibration, please contact your local 

distributor or service center for help. 

2)  Calibrate the output voltage measurement by configuring output voltage calibration (Refer to 

Program 16, section 3-7) in LCD setting to make sure the error between real output voltage and 

detected value of UPS is less than 1V.   

3)  Turn off each UPS (Refer to section 3-4-7.). Then, follow the wiring procedure in section 2-4.   
4)  Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one 

with the parallel cable and share current cable, and then screw the cover back. 

3-5-2. Turn on the parallel system in AC mode 

1)  Turn on the input breaker of each UPS. After all UPSs enter to bypass mode, measure the voltage 

between output L1 of each UPS with multimeter. If the voltage difference is less than 1V, that 

means all connections are correct. Otherwise, please check if the wirings are connected correctly.   

2)  Turn on the output breaker of each UPS. Before turning on each UPS in turns, check if PARXXX is 

displayed in each UPS sequentially. If no “PARXXX” exists in any UPS, please check if the parallel 

cables are connected correctly. 

3)  Turn on each UPS in turns. After a while, the UPSs will enter to AC mode synchronously and then, 

the parallel system is completed. 

3-5-3. Turn on the parallel system in Battery mode 

1)  Turn on the battery breaker (only available in long-run model and RT model) and output breaker of   

each UPS. 

NOTE: 

It’s not allowed to share one battery pack in parallel system. Each UPS should be connected 

to its battery pack.   

2)  Turn on any UPS. A few seconds later, the UPS will enter to battery mode.   
3)  Press the “ON” button to set up the power supply for another UPS, check if PARXXX is displayed. If 

not, please check if the parallel cables are connected correctly. Then Turn on another UPS. A few 

seconds later, the UPS will enter to battery mode and add to the parallel system.   

4)  If you have the third UPS, follow the same procedure of 3). Then, the parallel system is complete. 

Summary of Contents for 10KRT

Page 1: ...ONLINE UPS User Manual MASTER II SERIES 1P 1P RACK TOWER PRO800 QRS QRL 6KVA 10KVA Version 1 00 English...

Page 2: ...LE UPS INSTALLATION 7 2 5 UPS INSTALLATION FOR PARALLEL SYSTEM 9 2 6 SOFTWARE INSTALLATION 11 3 OPERATIONS 12 3 1 BUTTON OPERATION 12 3 2 LED INDICATORS AND LCD PANEL 12 3 3 AUDIBLE ALARM 14 3 4 SINGL...

Page 3: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Page 4: ...ed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary power switches installed in places away from the device to alert the electrical mainte...

Page 5: ...its own internal current source batteries The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fu...

Page 6: ...owing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option On...

Page 7: ...available for parallel model 3 External battery connector 4 Intelligent slot 5 RS 232 communication port 6 USB communication port 7 Emergency power off function connector EPO connector 8 Input circuit...

Page 8: ...module in 2U Assemble two feet and one short extension as one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module in the stands as shown in step 3 S...

Page 9: ...c shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and d...

Page 10: ...ld only connect to its supplied external battery pack The battery type and voltage may be different If you connect them together it maybe causes the hazard of electric shock or fire Warning Only for l...

Page 11: ...or Parallel System If the UPS is only available for single operation you may skip this section to the next 1 Install and wires the UPSs according to the section 2 3 2 Connect the output wires of each...

Page 12: ...10 Diagram 2 Wiring diagram of parallel system for tower model Diagram 3 Power cable connection for RT model Diagram 4 Wiring diagram of parallel system for RT model...

Page 13: ...11 2 6 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown...

Page 14: ...s button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press...

Page 15: ...y voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Page 16: ...operates in Bypass mode and supplies power to the loads via the bypass NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on the input breaker In Bypa...

Page 17: ...up time may be shorter than expected time 3 4 5 Battery mode operation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more th...

Page 18: ...it means that there are some problems for UPS operation Users can get the warning code from LCD panel Please check the 3 11 warning code table and the trouble shooting table in chapter 4 for details...

Page 19: ...e error between real output voltage and detected value of UPS is less than 1V 3 Turn off each UPS Refer to section 3 4 7 Then follow the wiring procedure in section 2 4 4 Remove the cover of parallel...

Page 20: ...le Then remove the unit from the parallel system Second method 1 If the bypass is abnormal you can not remove the UPS without interruption You must cut off the load and shut down the system 2 Make sur...

Page 21: ...to set up the UPS Refer to following diagram Programs available list for parameter 1 Code Description Bypass No output AC ECO CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Vol...

Page 22: ...60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output frequency will...

Page 23: ...range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose following two options DIS disab...

Page 24: ...ng Interface Setting Parameter 3 000 999 Set the maximum backup time from 0min to 999min UPS will shut down to protect battery after backup time arrives DIS Disable battery discharge protection and ba...

Page 25: ...ld be suitable to battery specifications 15 Inverter voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter voltage Parameter 3 the voltage range is from 0V to 6...

Page 26: ...se set up calibrated current as 3 Setting charging current 4A real measured current 3 7A 0 3A 3 8 Operating Mode Status Description If parallel UPS systems are successfully set up it will show one mor...

Page 27: ...lay Bypass mode Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes LCD display Battery Test De...

Page 28: ...PS 12V abnormal 6E None 3 10 Warning Indicator Warning Icon flashing Alarm Battery low Beeping every second Overload Beeping twice every second Battery unconnected Beeping every second Over charge Bee...

Page 29: ...ads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes fault Then UP...

Page 30: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Page 31: ...A 10 max 4 A 10 max 1 A 10 max 4 A 10 max Charging Voltage Battery number 13 65 V 1 PHYSICAL Dimension DXWXH mm UPS Unit 600 x 438 x 88 2U Battery Pack 688 x 438 x 88 2U UPS Unit 600 x 438 x 88 2U UPS...

Page 32: ...ERS INDONESIA Office PT PROLiNK INTIDATA NUSANTARA Walk In Jl Cideng Barat No 79 Jakarta Pusat 10150 Indonesia Email Support support id prolink2u com MALAYSIA Office FIDA SYSTEMS M SDN BHD Walk In 29...

Reviews: