6. Specifications

 

MODEL 

6KRT 

6KRTL 

10KRT 

10KRTL 

CAPACITY* 

6000 VA / 6000 W 

10000 VA / 10000 W 

INPUT 

Voltage Range 

Low Line Loss 

110 VAC(L-N) ± 3 % at 0-60% Load 

176 VAC(L-N) ± 3 % at 60%-100% Load 

Low Line Comeback 

Low Line Loss V 10V 

High Line Loss 

300 VAC(L-N) ± 3 % 

High Line Comeback 

High Line Loss Voltage - 10V 

Frequency Range 

46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system 

Phase 

Single phase with ground 

Power Factor 

 0.99 at 100% Load 

OUTPUT 

Output voltage 

208/220/230/240VAC 

AC Voltage Regulation   

± 1% 

Frequency Range   

(Synchronized Range) 

46Hz ~ 54 Hz @ 50Hz system;   

56Hz ~ 64 Hz @ 60Hz system 

Frequency Range (Batt. Mode) 

50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz 

Overload 

AC mode 

100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec 

Battery mode 

100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec 

Current Crest Ratio 

3:1 max 

Harmonic Distortion 

  1 % @ 100% Linear Load; 

  4 % @ 100% Non-linear Load 

Transfer Time 

Line

Battery 

0 ms 

Inverter

Bypass 

0 ms 

Inverter

ECO 

<10 ms (Typical) 

EFFICIENCY 

AC mode 

93.5% (max.) 

Battery Mode 

92% (max.) 

BATTERY 

Type 

12 V / 7 Ah 

Depending on 

applications 

12 V / 9 Ah 

Depending on 

applications 

Numbers 

16 

16~20** 

16 

16~20** 

Recharge Time 

7 hours recover to 90% 

capacity 

According to 

external battery 

pack 

9 hours recover to 

90% capacity 

According to external 

battery pack 

Charging Current   

1 A ± 10% (max.) 

4 A ± 10% (max.)  1 A ± 10% (max.) 

4 A ± 10% (max.) 

Charging Voltage   

(Battery number*13.65 V) ± 1%   

PHYSICAL 

Dimension, DXWXH(mm) 

UPS Unit: 600 x 438 x 

88 [2U] 

Battery Pack: 688 x 438 

x 88 [2U] 

UPS Unit: 600 x 438 

x 88 [2U] 

UPS Unit: 600 x 438 

x 88 [2U] 

Battery Pack: 688 x 

438 x 88 [2U] 

UPS Unit: 600 x 438 x 

88 [2U] 

Net Weight (kgs) 

UPS Unit: 17 

Battery Pack: 48 

UPS Unit: 17 

UPS Unit: 20 

Battery Pack: 48 

UPS Unit: 20 

IP Rating 

IP20(static) 

ENVIRONMENT

 

Operation Temperature 

0 ~ 40°C (the battery life will down when > 25°C) 

Operation Humidity 

<95 % and non-condensing 

Operation Altitude*** 

<1000m 

Acoustic Noise Level 

Less than 55dB @ 1 Meter 

Less than 58dB @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

 

Optional Battery Pack 

(20pcs) 

Battery Type 

12 V / 7 Ah 

12 V / 9 Ah 

Dimension, DxWxH (mm) 

600 x 438 x 133 [3U] 

600 x 438 x 133 [3U] 

Net Weight (kgs) 

57 

63 

* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC or when UPS is operated in 

parallel. 

**When using 16 pieces of batteries, the output power factor will be derated to 0.8. If using 18 or 19 pieces of batteries, the output power 

factor will be derated to 0.9. 

***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m. 

Product specifications are subject to change without further notice.

 

 

Summary of Contents for 10KRT

Page 1: ...ONLINE UPS User Manual MASTER II SERIES 1P 1P RACK TOWER PRO800 QRS QRL 6KVA 10KVA Version 1 00 English...

Page 2: ...LE UPS INSTALLATION 7 2 5 UPS INSTALLATION FOR PARALLEL SYSTEM 9 2 6 SOFTWARE INSTALLATION 11 3 OPERATIONS 12 3 1 BUTTON OPERATION 12 3 2 LED INDICATORS AND LCD PANEL 12 3 3 AUDIBLE ALARM 14 3 4 SINGL...

Page 3: ...nect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over them Do not b...

Page 4: ...ed Protection to the UPS as the standard safety would be infringed Warning labels should be placed on all primary power switches installed in places away from the device to alert the electrical mainte...

Page 5: ...its own internal current source batteries The UPS output sockets or output terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet In order to fu...

Page 6: ...owing chapter 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option On...

Page 7: ...available for parallel model 3 External battery connector 4 Intelligent slot 5 RS 232 communication port 6 USB communication port 7 Emergency power off function connector EPO connector 8 Input circuit...

Page 8: ...module in 2U Assemble two feet and one short extension as one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module in the stands as shown in step 3 S...

Page 9: ...c shock or fire NOTE Do not use the wall receptacle as the input power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and d...

Page 10: ...ld only connect to its supplied external battery pack The battery type and voltage may be different If you connect them together it maybe causes the hazard of electric shock or fire Warning Only for l...

Page 11: ...or Parallel System If the UPS is only available for single operation you may skip this section to the next 1 Install and wires the UPSs according to the section 2 3 2 Connect the output wires of each...

Page 12: ...10 Diagram 2 Wiring diagram of parallel system for tower model Diagram 3 Power cable connection for RT model Diagram 4 Wiring diagram of parallel system for RT model...

Page 13: ...11 2 6 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown...

Page 14: ...s button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press...

Page 15: ...y voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76...

Page 16: ...operates in Bypass mode and supplies power to the loads via the bypass NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on the input breaker In Bypa...

Page 17: ...up time may be shorter than expected time 3 4 5 Battery mode operation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more th...

Page 18: ...it means that there are some problems for UPS operation Users can get the warning code from LCD panel Please check the 3 11 warning code table and the trouble shooting table in chapter 4 for details...

Page 19: ...e error between real output voltage and detected value of UPS is less than 1V 3 Turn off each UPS Refer to section 3 4 7 Then follow the wiring procedure in section 2 4 4 Remove the cover of parallel...

Page 20: ...le Then remove the unit from the parallel system Second method 1 If the bypass is abnormal you can not remove the UPS without interruption You must cut off the load and shut down the system 2 Make sur...

Page 21: ...to set up the UPS Refer to following diagram Programs available list for parameter 1 Code Description Bypass No output AC ECO CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Vol...

Page 22: ...60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output frequency will...

Page 23: ...range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 ECO mode enable disable Interface Setting Parameter 3 Enable or disable ECO function You may choose following two options DIS disab...

Page 24: ...ng Interface Setting Parameter 3 000 999 Set the maximum backup time from 0min to 999min UPS will shut down to protect battery after backup time arrives DIS Disable battery discharge protection and ba...

Page 25: ...ld be suitable to battery specifications 15 Inverter voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter voltage Parameter 3 the voltage range is from 0V to 6...

Page 26: ...se set up calibrated current as 3 Setting charging current 4A real measured current 3 7A 0 3A 3 8 Operating Mode Status Description If parallel UPS systems are successfully set up it will show one mor...

Page 27: ...lay Bypass mode Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes LCD display Battery Test De...

Page 28: ...PS 12V abnormal 6E None 3 10 Warning Indicator Warning Icon flashing Alarm Battery low Beeping every second Overload Beeping twice every second Battery unconnected Beeping every second Over charge Bee...

Page 29: ...ads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overload too long and becomes fault Then UP...

Page 30: ...required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and...

Page 31: ...A 10 max 4 A 10 max 1 A 10 max 4 A 10 max Charging Voltage Battery number 13 65 V 1 PHYSICAL Dimension DXWXH mm UPS Unit 600 x 438 x 88 2U Battery Pack 688 x 438 x 88 2U UPS Unit 600 x 438 x 88 2U UPS...

Page 32: ...ERS INDONESIA Office PT PROLiNK INTIDATA NUSANTARA Walk In Jl Cideng Barat No 79 Jakarta Pusat 10150 Indonesia Email Support support id prolink2u com MALAYSIA Office FIDA SYSTEMS M SDN BHD Walk In 29...

Reviews: