6201-WA-DFNT
♦
ProLinx Wireless
Verify Data Exchange
High Speed Wireless EtherNet/IP Gateway
Page 34 of 45
ProSoft Technology, Inc.
August 12, 2008
4
Press "?" to display the Diagnostic menu.
5
Press "D" to display the Database menu.
6
Press "3" to show database registers beginning at 3000.
7
Press the "S" key to refresh the database values. The circled values in the
example should change each time you press the "S" key indicating that data
is being passed between modules. If these values do not change, contact
ProSoft Technical Support.
The data shown represents clock values originating from the 6201-WA-
DFNT_150 Client. The values are stored in 10 registers beginning with register
3000. The clock values are being passed wirelessly to the 6201-WA-DFNT Client
151. The 6201-WA-DFNT Client 151 module is taking this data and passing it
back to the 6201-WA-DFNT_150 Client and placing it into 5 registers beginning
at register 3005.