I n s t a l l a t i o n   G u i d e l i n e s

INSTALLATION CONTINUED

6

. Check that the polarity of the DC connections are correct: RED to positive (+) at

the battery and BLACK to negative (-) at the battery.

7

. Replace the fuse and/or switch on the breaker. A small spark is normal when this

connection is made.

Hardwiring the AC Output:

WARNING

: Fire, Shock and Energy Hazards

Make sure wiring is disconnected from all electrical sources before handling. All
wiring must be done in accordance with local and national wiring codes. Do not
connect the output leads of the inverter to any incoming AC source.

To Hardwire the AC Output Connections:

1

. Turn the inverter On/Off switch to Off.

2

. Locate the wiring box access panel, and remove the two screws to access the

wiring box as illustrated in Figure 5.

Figure 5 ~ Removing the Two Screws on the Wiring Box Access Panel

3

. Remove the wiring box access panel from the unit.

4

. Loosen the clamping nut of the Strain Relief.

5

. Locate the terminal block.

The three terminals are labeled as follows;
- L  Line
- N Neutral
- G  Ground

6

. Strip about 2 inches off the jacket of the AC output cable. The AC output cable

must be with in range of No. 14 to No. 16 AWG, have three conductors and be solid
or stranded.

G e n e r a l   O p e r a t i o n

OPERATION

The ON/Off switch turns the TruePower400 PS to ON or to Off.

- In the ON position, the Inverter / Fault LED light will illuminate Green. The TruePower400PS
   begins inverting and provides 400 watts of sine wave power, if shorepower is not present.
- In the Off position with no shorepower present, the TruePower400PS draws no current
  from the battery.
- In the Off position with the AC input cord plugged into shorepower, the AC Input LED
   light illuminates Green and the appliances connected to the TruePower400PS inverter
  can be operated.

NOTE: When the ON/Off switch is in the Off position with the TruePower400PS
connected to shorepower, AC voltage will be present at the output.

LED Indicators: The two indicator lights on the front panel of the inverter illustrate the
operating status of the TruePower400PS. See table 4 below.

Table 4 ~ Status of Indicator Lights

Can not run appliances as the AC
output is disabled in the invert mode.
Clear the fault condition. Reset the
TruePower400PS by turning the ON/Off
switch to Off and then back to ON, or
by connecting to shorepower.

Shorepower
ON

When the TruePower400PS is
connected to shorepower, the AC
Input illuminates.

Green

Can run all your appliances from
shorepower.

Inverter/Fault

Green

When the TruePower400PS unit
is on, the Inverter light illuminates.

Can run your appliances through the
TruePower400PS from the battery.

Inverter/Fault

Red

The Fault light illuminates
whenever there is a battery over-
voltage fault condition (in excess
of 15.6 volts), an output overload
condition or over-temperature
fault condition.

Light

               

Color

      

Status

 

            

Result

Solid Wire

L

Line

Neutral

Ground

Access screw location

AC OUTPUT WIRING

N
G

14 or 16 ga.
3 conductors
Solid

Stranded Wire

Access screw location

Figure 5

Ground

Neutral

Line

14 or 16 ga.
3 conductors
Stranded

L

G

N

AC OUTPUT WIRING

Summary of Contents for 79400

Page 1: ...om or call ProMariner directly at 1 800 824 0524 30 am to 5pm Eastern Time MPORTANT SAFETY NOTICE SAVE THESE INSTRUCTIONS ease read all safety operating and installation instructions before installing applying AC power to your ProMariner On Board Solutions power inverter odels Part No Description uePower400PS 79400 GFCI Protected Outlets uePower400PS 79405 Hardwired OnBoard Solutions A ProMariner ...

Page 2: ...ns on your recent purchase of the TruePower400PS Power Inverter or over 30 years ProMariner has been a leading designer and manufacturer of ower conversion products On Board Solutions serves customers in the automotive ecreational vehicle industrial and mobility markets and is a proud division of roMariner We have expanded our offering to include our latest line of ruePower400PS Power Inverters ea...

Page 3: ......

Page 4: ...to 400 watts of ontinuous power and with a surge rating of 1000 watts it can power complete ntertainmentsystemsincludingtwo27 televisions oritcouldalsopowersmallappliances hargers and power tools he TruePower400PS sine wave inverter includes a built in transfer switch that utomatically transfers between inverter and incoming AC power The inverter comes andard with dual AC outlets and AC hardwire c...

Page 5: ...shall be on the condition and agreement that Professional Mariner HALL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND Some states do not low the exclusion or limitation of incidental or consequential damages so the above limitations may not apply you ProfessionalMarinerneitherassumesnorauthorizesanypersonforanyobligationorliabilityinconnection ith the sale of this product o make...

Page 6: ...a short circuit GFCI opening enables the Reset and Test monthly capabilities Fan internal activates when the internal temperature of the inverter increases The fan speed varies with the internal temperature and turns off when the inverter cools down DC Input Cables AC Receptacles AC Input cord for shorepower Wiring box access panel Top panel AC Strain Relief for hardwiring 6 Chassis ground lug 7 R...

Page 7: ...e than 12 6 volts DC The inverter will automatically restart Turn the inverter to Off Disconnect the DC wiring Use proper wiring and ensure all connections are secure Problem Cause Solution AC input cord is connected to shorepower but appliance s arenotpoweredfromshorepower ACInputlightisilluminated GFCI has tripped Reset the external breaker Disconnect all appliances Check the AC wiring and press...

Page 8: ...lercablemaycausetheinvertertoshutdownunderaheavyload Ins talla tion G uide line s 6 Minimum Recommended DC Input cable copper AWG Minimum Recommended Cable Size AWG No 6 No 4 No 2 No 0 Cable Length Battery to Inverter Each Cable 0 10 Feet 10 15 Feet 15 30 Feet 30 40 Feet C Fuse and Disconnect or DC Circuit Breaker The DC fuse and disconnect switch or heDCcircuitbreakershallberated60amps Additional...

Page 9: ...r or ProMariner to have a qualified chnician inspect the unit esetting as the Result of an Overload he TruePower400PS has a high surge capacity of 1000 watts for 5 seconds the appliance s connected to the unit try to draw excess power for more than seconds the TruePower400PSwill shut down and the Red Fault light will illuminate fter removing the overload condition the TruePower400PS will cycle thr...

Page 10: ...ions Turn the inverter On Off switch to Off Locate the wiring box access panel and remove the two screws to access the iring box as illustrated in Figure 5 gure 5 Removing the Two Screws on the Wiring Box Access Panel Remove the wiring box access panel from the unit Loosen the clamping nut of the Strain Relief Locate the terminal block he three terminals are labeled as follows L Line N Neutral G G...

Page 11: ... either the ON or Off position verter Mode If the ON Off switch is in the ON position the TruePower400PS will utomatically supply the appliance s with the inverter power if the shorepower source ils or becomes disconnected NSTALLING YOUR REMOTE CONTROL Find a location for the remote with enough area to mount the 1 3 4 by 2 1 4 panel Using tape painters masking tape is preferred cover the area wher...

Reviews: