Service setting manual
50
ENG
Floor screed drying profile - factory setting:
PARAMETERS FOR FLOOR SCREED DRYING
Table with descriptions of parametres:
The procedure for F parameters setting is the same as the procedure for service
settings (see 38).
Group F1 contains the parameters for the setting of floor screed drying.
Para-
meter
Parameter name
Setting range
Default
setting
F1.1
FLOOR DRYING
0- NO
1- CIRCUIT 1
2- CIRCUIT 2
3- CIRCUIT 1 & 2
0
F1.2
INTERVAL 1: DURATION
1 ÷ 15 days
10
F1.3
INTERVAL 1: START TEMPERATURE
10 ÷ 60 °C
20
F1.4
INTERVAL 1: END TEMPERATURE
10 ÷ 60 °C
20
F1.5
INTERVAL 2: DURATION
1 ÷ 15 days
5
F1.6
INTERVAL 2: START TEMPERATURE
10 ÷ 60 °C
20
F1.7
INTERVAL 2: END TEMPERATURE
10 ÷ 60 °C
50
F1.8
INTERVAL 3: DURATION
1 ÷ 15 days
10
F1.9
INTERVAL 3: START TEMPERATURE
10 ÷ 60 °C
50
F1.10
INTERVAL 3: END TEMPERATURE
10 ÷ 60 °C
50
F1.11
INTERVAL 4: DURATION
1 ÷ 15 days
5
F1.12
INTERVAL 4: START TEMPERATURE
10 ÷ 60 °C
50
F1.13
INTERVAL 4: END TEMPERATURE
10 ÷ 60 °C
20