10.1.1 Parameter [WATER]
Mode
Menu
Archive
Reset
Parameter Water
Unit Stop
Water
Powder
Stirrer
Level
Pre rinse
Post rinse:
Flowrate Min:
A0825
Liquid
l/h
7
5
400.0
Fig. 24: Parameter [WATER]
Parameter
Factory setting
Adjustment range
Pre rinse
7 s
1 - 30 s
Post-rinse
5 s
1 - 30 s
Min. water supply
0 - 200000 l/h
Ultromat
Water supply
Min. water supply
400
1600
400
1000
4000
1000
2000
8000
2000
4000
14000
4000
If the current water supply is lower than the set minimum water supply, the
system generates a warning:
[Warning: Water supply too low.]
If the current water supply remains lower than the set minimum water
supply, then after 20 seconds the system generates a fault message:
[Fault: Water supply too low. Ultromat set to stop]
. The Ultromat interrupts
the preparation operation.
Operating Menu [F2]
46