Q2: How can I know which external alarm issues a warning (Alarm Status =
Enable
) from
alarm status in CLI?
A: Use this table that you can calculate which external alarm is warning (Alarm Status
=
Enable
)
.
Note that when the
Alarm Status
in the CLI is “0”, indicates warning on all ALARM_OUT; an
Alarm
Status
of “1” indicates ALARM_OUT 2, 3, 4, 5, 6, 7 and 8 have signal input; ALARM_OUT (
2
0
)
has no
warning.
Example #1
Alarm Status is “129” in CLI.
•
2
7
plus 2
0
equals 129 => ALARM_OUT._8 and ALARM_OUT_1 have no warning
Example #2
Alarm status is “255” in CLI .
•
No warning (signal output) on all alarms.