Promix-SM308
6
See operating voltage range in 5.2. Avoid supply of overvoltage.
Provide a reliable electriccontact. To prevent short-circuit, insulate places of
connection.
When the pusher is embedded in the lock (the door is closed), the output contacts 3-4 of the
sensor are closed 3-4 (5-4 are open); when the pusher is shifted out of the lock (the door is
open), the output contacts 3-4 of the sensor are open (5-4 are closed).
Example of the lock connection to the remote control system Promix-RDS.
7.
SPECIAL ASPECTS OF INSTALLATION AND
OPERATION
1) The possibility of using the lock and the place of installation (outdoors or indoors) are
determined by the
installation organization
on the basis of the design features and the lock
operating principle, method of installation, room criticality level, the purpose of the access
restriction regime and other factors (the presence of security providers, video surveillance,
etc.).
2) To prevent deformations of the door due to attempts to open the door with the lock closed, it is
recommended to mount the lock in the area of the door handle.
3) It is recommended to install the lock together with a door closer
– this reduces impact load on
the lock and extends its service life.
8.
TROUBLE-SHOOTING
Troubles and problems
Remedies
The lock does not fix the latch (the door is
not fixed in the closed state).
Check the absence of supply voltage.
Adjust the latch position (see 6.1) so that the
latch, with the door closed, enters the lock slot
until the catch hook operates.
The latch does not enter the lock slot, or
enters with friction.
Restore position of the door that changed in the
course of operation. If restoration is impossible,
adjust the latch (see 6.1)
Lock
Controller Promix-CR.RX
Remote control
Promix-CR.TX
~220 V