The detector should be mounted vertically as the sensor head pointing downwards. Detector
has to be mounted such that the sensor's gas entrance area.
The install location
•
should be isolated from vibration, direct sun light and have temperature stability
•
avoided external influences such as splashing water, oil, corrosive aerosols
•
should have at least 30 cm free space beneath the sensor head to provide accessibility
for calibration work.
•
should be in air flow between possible leak or collection point and possible source of
ignition.
Prosense do not recommend to install detectors to :
•
directly above a cooking unit,
•
directly above a sink unit,
•
close to an extractor unit,
•
outdoor without protection against the rain,
•
in places where temperature is outside the admissible operating range,
•
in corrosive environments,
•
inside air vents.
•
in environments where silicon can be found.
The Prosense detector has an integrated mounting screw holes on the body. The correct
mounting position is given in Diagram 3:
Diagram 3: Mounting holes on body
Mounting hole
Mounting hole
Mounting hole