MVI56E-AFC / MVI69E-AFC ♦ Enhanced Liquid and Gas Flow Computer
Configuring Primary Input Characteristics
ControlLogix® and CompactLogix™
Setup and Configuration Guide
ProSoft Technology, Inc.
Page 94 of 151
13 Configuring Primary Input Characteristics
Parameter
Description
Measured quantity
This value specifies the physical property of the fluid that is
measured directly or indirectly by the primary input.
Mass
Energy (heating value)
Gross volume (volume at operating conditions)
For some meter types (notably a traditional orifice), this value is
fixed and cannot be changed.
For a linear (pulse) meter it characterizes the K-factor.
For a traditional pulse meter such as a turbine, this quantity is
Gross Volume.
Flow input unit
This value specifies the engineering units base and scaling of the
measured quantity selected for the primary input.
For some meter types, for example a traditional orifice, this value
is fixed and cannot be changed.
For a linear (pulse) meter, it specifies K-Factor characteristics.
Flow Rate Period
This value specifies the time period to which the primary input
flow rate is referenced.
Second
Minute
Hour
Day
For all meter types except flow rate integration, this value is fixed
and cannot be changed.