MVI56E-AFC / MVI69E-AFC ♦ Enhanced Liquid and Gas Flow Computer
Configuring K-factor Characteristics
ControlLogix® and CompactLogix™
Setup and Configuration Guide
ProSoft Technology, Inc.
Page 96 of 151
The K-factor itself is entered as a stream parameter. The K-factor units available for
selection will depend on the selected measured quantity.
For a linear (pulse) meter:
Gross volume = (pulses/K-factor) x meter factor
The K-factor is a factor that converts raw pulse count (from the Pulse Meter) to a volume
and is expressed as
Pulses per unit volume
, such as "1000 pulses per gallon" or
"3578.224 pulses per cubic meter". This number, found on the
manufacturer’s datasheet
for the meter, is determined at the factory for the specific unit before shipping. Dividing
"pulses" by "pulses per gallon" gives you "gallons". API calls the value
“
pulses / K-factor"
as "indicated volume
”
.
Summary of Contents for MVI56E-AFC