MVI56E-AFC / MVI69E-AFC ♦ Enhanced Liquid and Gas Flow Computer
Configuring Meter Groups
ControlLogix® and CompactLogix™
Setup and Configuration Guide
ProSoft Technology, Inc.
Page 56 of 151
5.3
Configuring Meter-Group Members
The meter
“group-member” (member of some group, the parent of which is identified by
giving its meter-channel number). This distinction is made by the value of
Group
membership
field, which if zero indicates an “autonomous” meter (and textually
confirmed as so by the adjacent label, and if non-
zero indicates a “group-member” meter
(and textually confirmed as so by the adjacent label reading “Member of group”) and is
the 1-based number of the group-parent which itself has its
Metering principle
dropdown
configured as “Meter-group parent”.
Note: The meter-group parent must be configured prior to the members of the group.
To configure meter-group members:
1
From the
P
ROJECT
menu, select
M
ETER
C
ONFIGURATION
.
The
Meter Configuration
dialog displays.
2
In the
Select Meter
area, select the meter to configure.
3
In the
Meter Classification
area, select the same product group and system of units
that you selected for the parent.