MVI56E-AFC / MVI69E-AFC ♦ Enhanced Liquid and Gas Flow Computer
Configuring Common Parameters
ControlLogix® and CompactLogix™
Setup and Configuration Guide
ProSoft Technology, Inc.
Page 72 of 151
You may configure the accumulator quantity to be used for each archive accumulator
using the EAFC Manager (
M
ETER
C
ONFIGURATION
>
A
RCHIVE
C
ONFIG
>
A
CCUMULATOR
S
ELECT
):
6.7.3 Net Accumulator Calculation
The Net Accumulator Calculation depends on the product group (gas or liquid).
For gas applications, the Net Accumulator is calculated as follows:
Converts to Reference
Temperature and Pressure
Gross Accumulator
Net Accumulator
For liquid applications (all except Emulsion), the Net Accumulator is calculated as
follows:
Converts to Reference
Temperature and Pressure
Subtracts Water
Gross Accumulator
Gross Standard
Accumulator
Net Accumulator
Water
For liquid applications (Oil-Water Emulsion), the net accumulator is calculated as
follows, using API ch 20.1:
Summary of Contents for MVI56E-AFC
Page 78: ......