PLX82-EIP-PNC ♦ Communication Gateway
Diagnostics and Troubleshooting
EtherNet/IP™ Server to PROFINET Controller
User Manual
ProSoft Technology, Inc.
Page 113 of 154
July 24, 2018
9.3.2 General Diagnosis
The
General Diagnosis
pane provides information on the device state as well as
other general diagnostic parameters.
LED
Description
Color
Device State
Communication
Indicates whether the PROFINET device executes
during network communication.
Green
- In communication
state
Gray
- Not in communication
state
Run
Indicates whether the PROFINET device has been
configured correctly
Green
- Configuration OK
Gray
- Incorrect configuration
Ready
Indicates whether the PROFINET device has been
started correctly. The PROFINET device waits for a
configuration.
Yellow
- Device is Ready
Gray
- Device is not ready
Error
Indicates whether the PROFINET device recorded a
device status error (see
Extended Diagnosis
)
Red
- Error
Gray
- No Error
Network State
Operate
Indicates whether the PROFINET device is in data
exchange. In a cyclic data exchange, the input or
output data is transmitted to the PROFINET device.
Green
- In Operation state
Gray
- Not in Operation state
Idle
Indicates whether the PROFINET is in Idle state
Yellow
- In Idle state
Gray
- Not in Idle state
Stop
Indicates whether the PROFINET device is in Stop
state. There is no cyclic data exchange on the
PROFINET network. The PROFINET device was
stopped by the application program, or it changed
the Stop state because of a bus error.
Red
- In Stop State
Gray
- Not in Stopped state
Offline
The PROFINET device configuration is offline as
long as it does not have a valid configuration.
Yellow
- In Offline state
Gray
- Not in Offline state
Configuration
State
Configuration
locked
Indicates whether the PROFINET device
configuration is locked to avoid configuration data
writeover.
Yellow
- Configuration locked
Gray
- Configuration not
locked
New Configuration
pending
Indicates whether a new PROFINET device
configuration is available.
Yellow
- New configuration
pending
Gray
- No new configuration
pending
Reset Required
Indicates whether a firmware reset is required as a
new PROFINET device has been loaded into the
device
Yellow
- Reset required
Gray
- No reset required
Bus On
Indicates whether the bus communication was
started or stopped (i.e., whether the device is active
on the bus or not bus communication to the device
is possible and no response messages are sent
Green
- Bus On
Gray
- Bus Off