PLX82-EIP-PNC ♦ Communication Gateway
Diagnostics and Troubleshooting
EtherNet/IP™ Server to PROFINET Controller
User Manual
ProSoft Technology, Inc.
Page 135 of 154
July 24, 2018
9.3.9 EIP Status Data in Upper Memory
The EIP driver has an associated status data area located in the PLX82-EIP-
PNC
’s upper memory. The
Data Map
functionality of the PLX82-EIP-PNC can be
used to map this data into the normal user data range of the PLX82-EIP-PNC
’s
database.
Note that all the status values are initialized to zero (0) at power-up, cold boot
and during warm boot.
EIP Server Status Data
The following table lists the addresses in upper memory where the PLX82-EIP-
PNC stores status data for each EIP server.
EIP Server
Address Range
0
11000 through 11015
1
11016 through 11031
2
11032 through 11047
3
11048 through 11063
4
11064 through 11079
The content of each server’s status data area is structured the same. The
following table describes the content of each register in the status data area.
Offset
Description
0 through 1
Connection State
2 through 3
Open Connection Count
4 through 5
Socket Read Count
6 through 7
Socket Write Count
8 through 15
Peer IP
EIP Client Status Data
The following table lists the addresses in upper memory the PLX82-EIP-PNC
stores general error and status data for each EIP connected and unconnected
client.
EIP Client
Address Range
Connected Client 0
12000 through 12109
Connected Client 1
12400 through 12509
Unconnected Client 0
12600 through 12709