PLX82-EIP-PNC ♦ Communication Gateway
Configuring the EtherNet/IP Driver
EtherNet/IP™ Server to PROFINET Controller
User Manual
ProSoft Technology, Inc.
Page 43 of 154
July 24, 2018
Class 3 Client/UClient [x] Commands SLC500 2 Address Fields
Parameter
Value
Description
Enable
Enable
Disable
Conditional Write
Specifies if the command should be executed and under what conditions.
Enable - The command is execute each scan of the command list.
Disable - The command is disabled and will not be executed.
Conditional Write - The command executes only if the internal data
associated with the command changes.
Internal Address
0 to 9999
Specifies the database address in the module's internal database to be
associated with the command. If the command is a read function, the data
received in the response message is placed at the specified location. If the
command is a write function, data used in the command is sourced from a
specified data area.
Poll Interval
0 to 65535
Specifies the minimum interval to execute continuous commands. The
parameter is entered in 1/10 of a second. If a value of 100 is entered for a
command the command executes no more frequently that every 10 seconds.
Reg Count
1 to 125
Specifies the number of data points to be read from or written to the target
audience.
Swap Code
None
Word Swap
Word and Byte Swap
Byte Swap
Specifies if the data from the server is to be ordered differently than it was
received. This parameter is typically used when dealing with floating-point or
other multi-register values.
None - No change is made (abcd)
Word Swap - The words are swapped (cdab)
Word and Byte Swap - The words and bytes are swapped (dcba)
Byte Swap - The bytes are swapped (badc).
IP Address
xxx.xxx.xxx.xxx
Specifies the IP address of the target device to be addressed by this
command.
Slot
-1
Use a value of -1 when interfacing to an SLC 5/05. These devices do not have
a slot parameter. When addressing a processor in a ControlLogix or
CompactLogix rack, the slot number corresponds to the slot in the rack
containing the controller being addressed.
Func Code
501
509
Specifies the function code to be used in the command.
501 - Protected Typed Read
509 - Protected Typed Write
File Type
Binary
Counter
Timer
Control
Integer
Float
ASCII
String
Status
Specifies the file type to be associated with the command.
File Number
-1
Specifies the PLC-5 file number to be associated with the command. If a value
of -1 is entered for the parameter, the field will not be used in the command,
and the default file will be used.
Element Number
Specifies the element in the file where the command will start.
Comment
This field can be used to give a 32-character comment to the command.