PLX82-EIP-PNC ♦ Communication Gateway
Acyclic Data
EtherNet/IP™ Server to PROFINET Controller
User Manual
ProSoft Technology, Inc.
Page 85 of 154
July 24, 2018
Configure Message for Write and Response
1
Expand the
PLX82.ACYCLIC.W
RITE
.R
EQUEST
controller tag.
2
Write also contains the
PLX82.ACYCLIC.Write.Request.Length
. Here, you
specify the length of the data to be returned. The recommended limit is 495
bytes.
Controller Tag
Description
PLX82.ACYCLIC.Write.
Request.DeviceID
You can get the device ID from the Device table described under "Viewing the
Device Table" in this manual. The Device ID is list in the Index column of the
table. Remember that devices in the table start with the first device as 0,
regardless of what number is displayed with the device. The second device in
the table represents 1, the next device 2, and so on.
PLX82.ACYCLIC.Write.
Request.SlotNumber
Specify the slot number of the device. You can find this information in the
Address table described in the section entitled "Viewing and Modifying the
Address Table" in this manual.
PLX82.ACYCLIC.Write.
Request.SubSlotNumber
Specify the sub-slot number of the device. You can find this information in the
Address table described in the section entitled "Viewing and Modifying the
Address Table" in this manual.
PLX82.ACYCLIC.Write.
Request.Index
Enter the device index number. This should be available fro the device
manufacturer documentation.
PLX82.ACYCLIC.Write.
Request.Length
495 bytes
3
The Write Results are displayed in the
PLX82.ACYCLIC.W
RITE
.R
ESPONSE
controller tag.