Diagnostics and Troubleshooting
PLX82-EIP-PNC ♦ Communication Gateway
User Manual
EtherNet/IP™ Server to PROFINET Controller
Page 92 of 154
ProSoft Technology, Inc.
July 24, 2018
9.1
LEDs
All LEDs are found on the front of the module.
LED
State
Description
Pwr
OFF
Power is not connected to the power terminals or source is insufficient to properly
power the gateway (200mA at 24 VDC is required)
Solid GREEN
Power is connected to the power terminals. Verify that the other LEDs for
operational and functional status come on briefly after power-up (check for burned-
out LEDs).
Flt
OFF
Normal operation
Solid RED
A critical error has occurred. Program executable has failed or has been user-
terminated and is no longer running. Press Reset p/b or cycle power to clear error.
Cfg
OFF
Normal operation
Solid AMBER
The unit is in configuration mode. Either a configuration error exists, or the
configuration file is currently being downloaded or read. After power up, the
configuration is read, and the unit implements the configuration values and initiates
the hardware. This occurs during power cycle or after the Reset button is pressed.