Functional Overview
ProLinx-HART ♦ ProLinx Gateway
Driver Manual
HART Master with Analog I/O
Page 22 of 104
ProSoft Technology, Inc.
October 13, 2011
With the auto-poll feature enabled, the module automatically generates the following
HART commands and stores the data in the module's database at the user-specified
location:
CMD
Description
0
Read Unique Identifier
3
Read Current and Four Dynamic Variables
13
Read Tag, Descriptor and Date
14
Read PV Sensor Information
15
Read Output Information
If the unit is set for point-to-point mode, the module will automatically gather the
information for the device with the polling address (short address) of zero and place the
data into the database. Each device requires a 50-word database area with the format
shown in the following table.
DB Byte
Offset
Type
Description
Byte
Cnt
Data
Source
Use of Data
0
byte
Auto-polling command status bits
1
App
Status
1
byte
Last first status byte received from
device
1
Resp
Status
2
byte
Last second status byte received
from device
1
Resp
Status
3
byte
Manufacture ID Code
1
CMD 0
LongAddress
4
byte
Device Type Code
1
CMD 0
LongAddress
5
byte
Minimum number of preambles
1
CMD 0
Msgconstruction
6
byte
Universal Command Major Rev #
1
CMD 0
Msgchoice
7
byte
Device Revision Level
1
CMD 0
Info
8
byte
Software Revision Level
1
CMD 0
Info
9
byte
Hardware Revision Level/Physical
Signaling Code
1
CMD 0
Info
10
byte
Device Flags
1
CMD 0
Info
11 to 13
byte
Device ID
3
CMD 0
Long Address
14
byte
Minimum number of preambles to
be sent with the response message
from the slave to the master.
1
CMD 0
15
byte
Maximum number of device
variables
1
CMD 0
Info
16 to 17
word
Configuration Change Counter
2
CMD 0
Info
18
byte
Extended Field Device Status
1
CMD 0
Info
19
byte
Primary variable units code
1
CMD 3
Cfg
20
byte
Secondary variable units code
1
CMD 3
Cfg
21
byte
Tertiary variable units code
1
CMD 3
Cfg
22
byte
Quaternary variable units code
1
CMD 3
Cfg
23 to 30
byte
Tag name
8
CMD 13
Info
31 to 46
byte
Descriptor
16
CMD 13
Info
47 to 49
byte
Tag/Descriptor data
3
CMD 13
Info
50 to 52
byte
Transducer serial number
3
CMD 14