Reference
ProLinx-HART ♦ ProLinx Gateway
Driver Manual
HART Master with Analog I/O
Page 68 of 104
ProSoft Technology, Inc.
October 13, 2011
COMMAND 46 - Trim DAC Gain
Description
This command calibrates the device Digital to analog converter gain. This is done by
writing the same current value that is measured in the loop.
Write Parameters
Word
High Byte
Low Byte
0
Floating Point Measured Current (mA)
1
Floating Point Data Returned
Word
High Byte
Low Byte
0
Floating Point Current (mA)
1
Integer Data Returned
Word
High Byte
Low Byte
0
STATUS WORD