ProLinx-HART ♦ ProLinx Gateway
Reference
HART Master with Analog I/O
Driver Manual
ProSoft Technology, Inc.
Page 73 of 104
October 13, 2011
COMMAND 51 - Write Dynamic Variable Assignments
Description
This command sets the assignment of the Dynamic Variables returned with command 3.
Write Parameters
Word
High Byte
Low Byte
0
Transmitter Variable Code For Primary
Variable
Transmitter Variable Code For Second
Variable
1
Transmitter Variable Code For Third
Variable
Transmitter Variable Code For Fourth
Variable
Floating Point Data Returned
NONE
Integer Data Returned
Word
High Byte
Low Byte
0
STATUS WORD
1
Transmitter Variable Code For Primary
Variable
Transmitter Variable Code For Second
Variable
2
Transmitter Variable Code For Third
Variable
Transmitter Variable Code For Fourth
Variable