5.5.2 RS-232 Configuration/Debug Port
This port is physically an RJ45 connection. An RJ45 to DB-9 adapter cable is
included with the module. This port permits a PC based terminal emulation
program to view configuration and status data in the module and to control the
module. The cable for communications on this port is shown in the following
diagram:
Disabling the RSLinx Driver for the Com Port on the PC
The communication port driver in
RSLinx
can occasionally prevent other
applications from using the PC’s COM port. If you are not able to connect to the
module’s configuration/debug port using
ProSoft Configuration Builder (PCB)
,
HyperTerminal
or another terminal emulator, follow these steps to disable the
RSLinx
Driver.
1
Open
RSLinx
and go to
C
OMMUNICATIONS
>RSW
HO
2
Make sure that you are not actively browsing using the driver that you wish to
stop. The following shows an actively browsed network:
3
Notice how the DF1 driver is opened, and the driver is looking for a processor
on node 1. If the network is being browsed, then you will not be able to stop
this driver. To stop the driver your
RSWho
screen should look like this: