MVI46-S3964R
♦
SLC Platform
Module Configuration
Siemens 3964R Protocol
Page 26 of 74
ProSoft Technology, Inc.
2.5.2 Baud
Rate
300 to 115200
This parameter specifies the baud rate to be used on the port. Valid values are
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200.
2.5.3 Parity
N, O, E
This parameter specifies the parity setting for this port. Valid values are N =
None, O = Odd, E = Even.
2.5.4 Data
Bits
7 or 8
This parameter specifies the number of message data bits. Valid values are 7 or
8 bits.
2.5.5 Stop
Bits
1 or 2
This parameter specifies the number of message stop bits. Valid values are 1 or
2 stop bits.
2.5.6 RTS
On
Delay (in milliseconds) after RTS before message is sent.
2.5.7 RTS
Off
Delay (in milliseconds) after message before RTS dropped.
2.5.8 Minimum Response Delay
The minimum amount of time in milliseconds to wait before responding to a CP
message.
2.5.9 Use CTS Line
Yes or No
This parameter specifies whether or not to monitor CTS modem line.
2.5.10 Swap
0 or 1
This parameter specifies whether bytes should be swapped. 0 = No data byte
swapping, 1 = Data byte swapping.
April 17, 2008