MVI56-PDPMV1 ♦ ControlLogix Platform
Diagnostics and Troubleshooting
PROFIBUS DPV1 Master
User Manual
Page 195 of 251
ProSoft Technology, Inc.
Byte 2 - Station Status 3 Bits
Bit
Description
0
Reserved
1
Reserved
2
Reserved
3
Reserved
4
Reserved
5
Reserved
6
Reserved
7
Extended diagnostic overflow
Byte 3 - Master Address
This byte shows the address of the assigned PROFIBUS Master after
parameterization. If there is an error during the parameterization process, this
byte will display the value FF (hexadecimal).
Byte 4 - Ident Number High
This byte shows the high byte of the specific Ident Number assigned to the
module by the PROFIBUS User Organization.
Byte 5 - Ident Number Low
This byte shows the low byte of the specific Ident Number assigned to the
module by the PROFIBUS User Organization.