Configuring Meter Parameters
MVI69E-AFC ♦ Version 4.04
Page 48 of 145
ProSoft Technology, Inc.
December 18, 2018
The settings in the
End of Period
section for the meter now take precedence over
those set on the Site page.
Sample rate alarming
– This is the longest period that can elapse between
successive fresh samples of process input values without raising the “sample
rate too low” alarm. This value is specified in seconds with a range of 0 through
30. Zero “0” means that the sample rate test is not performed and alarms are not
raised. The complete implementation requires supporting logic in the PLC. The
default for gas product is 1 second and for any liquid product is 5 seconds.
4.3.2 Setting a Stream Name
1
To set a
Stream Name
, click on the
I
DENTIFICATION
button under the
Stream Enabled
indicator.
2
Enter a product description and click
OK
.