MVI69E-AFC ♦ Version 4.04
Module Installation
ProSoft Technology, Inc.
Page 103 of 145
December 18, 2018
15 Installing the Module in the Rack
If you have not already installed and configured your processor and power
supply, please do so before installing the MVI69E-AFC. Refer to the processor
documentation for installation instructions.
Warning: You must follow all safety instructions when installing this or any other electronic
devices. Failure to follow safety procedures could result in damage to hardware or data, or even
serious injury or death to personnel. Refer to the documentation for each device you plan to
connect to verify that suitable safety procedures are in place before installing or servicing the
device.
After you have checked the placement of the jumpers, insert the MVI69E-AFC
into the rack. Use the same technique recommended by the processor
manufacturer to remove and install MVI69E-AFC modules.
Warning: When you insert or remove the module while backplane power is on, an electrical arc
can occur. This could cause an explosion in hazardous location installations. Verify that power is
removed or the area is non-hazardous before proceeding. Repeated electrical arcing causes
excessive wear to contacts on both the module and its mating connector. Worn contacts may
create electrical resistance that can affect module operation.
Note: If you insert the module improperly, the system may stop working, or may behave
unpredictably.
15.1 Module Initialization
When the module is powered up for the first time, both the
OK
and
ERR
NVRAM
LEDs are illuminated. This indicates that the module is in the
Cold Start
state and
is not yet ready to perform calculations. The following steps initialize the module:
Configure Site Parameters
Enable at least one meter
Set the processor to RUN mode
After these three steps are accomplished, the state is changed from
Cold Start
to
Released
. This indicates that that module is ready to perform flow calculations.
When in the
Released
state, the
OK
LED is ON and the
ERR
LED is off.
When the module is ready, you will use EAFC Manager to monitor meter
operation, archives, and events.
Summary of Contents for MVI69E-AFC
Page 8: ......
Page 20: ......
Page 44: ......
Page 76: ......
Page 80: ......
Page 88: ......
Page 92: ......
Page 94: ...Density Units MVI69E AFC Version 4 04 Page 94 of 145 ProSoft Technology Inc December 18 2018...
Page 96: ......
Page 102: ......
Page 104: ......
Page 108: ......
Page 138: ......
Page 140: ...What s Next MVI69E AFC 4 04 Page 140 of 145 ProSoft Technology Inc December 18 2018...
Page 144: ......