Reference 104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 128 of 157
ProSoft Technology, Inc.
January 22, 2010
Status Register Name
Description
10254
…
10263
Host IP Address
(socket 1)
IP address of the client connected to the server.
10264
StartDT active (socket 1)
This word contains the current StartDT state as
follows:
0 = The gateway has not received the most recent
STARTDT request through this socket or there has
been no communication with the remote host unit.
1 = The gateway has received the most recent
STARTDT request through this socket (therefore
will be reporting data to the remote client
connected through this socket).
10223
…
10299
No Valid Data (socket 1)
Not Used.
5.4 Command
Qualifiers
Qualifier Code
Description
0
No additional definitions (Module will use Long duration pulse for this qualifier
selection).
1
Short pulse duration (circuit breaker), determined by user-set parameter in
gateway. This is supported in the gateway for single and dual point commands.
2
Long duration pulse (control relay), duration determined by user-set parameter
in gateway. This is supported in the gateway for single and dual point
commands.
3
Persistent output of control. This is supported in the gateway for all output data
types.
4 to 8
Reserved for standard definitions of standard - NOT SUPPORTED
9 to 15
Reserved for the selection of other predefined functions - NOT SUPPORTED
16 to 31
Reserved for special use (private range) - NOT SUPPORTED