104S
♦
ProLinx Gateway
Configure the Gateway
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 19 of 157
January 22, 2010
Time DB Offset
-1
or
0
to
3994
This parameter sets the location in the database where the gateway’s current date
and time will be copied to.
Note:
The following tables lists the 12-byte data area placed in the database if the Time DB Offset
parameter is set to a value other than -1:
Byte Length
Range
Description
0 to 1
2
0 to 59,999
Seconds and milliseconds
2
1
0 to 59
Minutes
3
1
0 to 23
Hour
4 1
Reserved
5
1
1 to 31
Day of the Month
6
1
1 to 12
Month
7 to 8
2
0 to 65,535
Year (four digit format, for example 2005)
9 1
Reserved
10
1
0 or 1
Invalid Flag (0 = Valid, 1 = Invalid
11 1
Reserved
Command Delay Timer
1000
to
60000
milliseconds
This value is used for time-tag validity verification for the ASDUs listed below. The
received commands will only be accepted if [tim Command Delay Timer] is
greater than the gateway's own time.
58: Single command with time tag CP56Time 2a
59: Double command with time tag CP56Time 2a
60: Regulating step command with time tag CP56Time 2a
61: SetPoint command, normalized value with time tag CP56Time 2a
62: SetPoint command, scaled value with time tag CP56Time 2a
63: SetPoint command, short floating point with time tag CP56Time 2a
107: Test command with time tag CP56Time2a
If the value is less than
1000
milliseconds, the gateway will default to
5000
milliseconds
Maximum ASDU Resp Len
25
to
246
This parameter limits the maximum size of the ASDU portion of a response
message. Most applications will use a value of
246
.