Configure the Gateway
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 20 of 157
ProSoft Technology, Inc.
January 22, 2010
Freeze Start Type
D
=
D
AY
,
H
=
H
OUR
,
M
=
M
INUTE
,
N
=
N
OT USED
The Freeze Start Type parameter defines when the gateway starts sending the M_IT
messages.
Interval for Freeze
0
to
65535
Freeze Start Type and Interval for Freeze are used if Mode A operation is to be used
for the counter freeze operation. If they are not used, the gateway will operate in
Mode D.
Common Address of ASDU
0
to
65535
This parameter specifies the common address of the ASDU (section address) for
access to data in the gateway. There is only one value entered for access to all data
in the gateway.
Cyclic Data Transmission
0
to
4,294,967,296
(2 raised to the power of 32)
This parameter defines the number of milliseconds between cyclic updates. The
range of values for this parameter permit update times of 1 millisecond to 5 minutes.
If the parameter is set to 0, cyclic data reporting will be disabled.
Select/Operate Timeout
0
to
4,294,967,296
(2 raised to the power of 32)
This parameter sets the number of milliseconds after a select command is received
in which to wait for a valid execute command. The range of values for this parameter
permit times of 1 millisecond to 30 seconds. If the parameter is set to 0, the feature
will be disabled.
Use ACTTERM with Setpoint
1
or
0
This parameter determines if an ACTTERM will be sent. If the parameter is set to 1,
then setpoint commands will issue an ACTTERM when the command is complete. If
the parameter is set to 0, ACTCON is the last response to a setpoint command.