104S
♦
ProLinx Gateway
Configure the Gateway
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 21 of 157
January 22, 2010
Use ACTTERM with Step
1
or
0
This parameter determines if an ACTTERM will be sent. If the parameter is set to 1,
then step commands will issue an ACTTERM when the command is complete. If the
parameter is set to 0, ACTCON is the last response to a step command.
Event Scan Delay
1
to
65535,
or
0
to disable
If set to 0, the feature will be disabled and the gateway will not generate any events.
If set from 1 to 65535, the parameter represents the number of milliseconds between
event scanning. This parameter defines how often the program will scan for new
events in the databases.
Set Priority Queues
Y
ES
or
N
O
This section defines priority queues for the gateway. You can assign priorities to
data types that can return events so that events of M_IT_NA data types will be
returned before other data types. This may cause events to be lost as the event
buffers for low priority queues may overflow. If this feature is utilized, each data type
must be assigned a unique index from 0 to 7. The lower the index, the higher the
priority (0=highest priority).